Plan Review Notes
Plan Review Notes For Permit 02061124
Permit Number 02061124
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-06-21 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING AND AFTER CONSTRUCTION.
  
 2) FIRE DEPARTMENT CONNECTIONS ARE TO
 BE LOCATED NO FARTHER THAN 150 FEET
 FROM FIRE HYDRANTS.
  
 3) THERE APPEARS TO BE SOME CONFUSION
 WITH SP1 AND SP4. FIRE HYDRANTS AND
 FIRE DEPARTMENT CONNECTIONS ARE
 SEPARATE DEVICES AND SHOULD BE SHOWN
 AS SEPARATE DEVICES.
  
 4) ALL ENTRY GATES ARE TO BE PERMITTED
 SEPARATELY. ALL ENTRY WAYS SHALL BE
 AT LEAST 20 FEET IN CLEAR WIDTH.
 PROVISIONS ARE TO BE MADE FOR FIRE
 AND PARAMEDICAL ACCESS. IF ELECTRIC,
 PROVISIONS ARE TO BE MADE FOR ACCESS
 WHEN POWER IS LOST.
  
 5) POST INDICATOR VALVES ARE REQUIRED.
  
 6) FIRE LINE BACKFLOW DEVICE(S) ARE TO
 BE SUPERVISED WITH TAMPER SWITCHES AND
 BE CHAINED AND LOCKED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL