| Plan Review Notes For Permit 02061124 |
| Permit Number |
02061124 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-21 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO,DURING AND AFTER CONSTRUCTION. | | | | | | 2) FIRE DEPARTMENT CONNECTIONS ARE TO | | | BE LOCATED NO FARTHER THAN 150 FEET | | | FROM FIRE HYDRANTS. | | | | | | 3) THERE APPEARS TO BE SOME CONFUSION | | | WITH SP1 AND SP4. FIRE HYDRANTS AND | | | FIRE DEPARTMENT CONNECTIONS ARE | | | SEPARATE DEVICES AND SHOULD BE SHOWN | | | AS SEPARATE DEVICES. | | | | | | 4) ALL ENTRY GATES ARE TO BE PERMITTED | | | SEPARATELY. ALL ENTRY WAYS SHALL BE | | | AT LEAST 20 FEET IN CLEAR WIDTH. | | | PROVISIONS ARE TO BE MADE FOR FIRE | | | AND PARAMEDICAL ACCESS. IF ELECTRIC, | | | PROVISIONS ARE TO BE MADE FOR ACCESS | | | WHEN POWER IS LOST. | | | | | | 5) POST INDICATOR VALVES ARE REQUIRED. | | | | | | 6) FIRE LINE BACKFLOW DEVICE(S) ARE TO | | | BE SUPERVISED WITH TAMPER SWITCHES AND | | | BE CHAINED AND LOCKED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
|