| 2002-12-05 00:00:00 | **************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE NOTE NOTES AND ITEMS FROM |
| | PREVIOUS REVIEW WERE NOT ADDRESSED AND |
| | PLANS STILL DO NOT CORRELATE. |
| | THERE ARE MANY ITEMS ON RISER DIAGRAM |
| | THATSTILL DO NOT CORRELATE WITH |
| | PANEL SCHEDULES/PANELS. |
| | |
| | 2)NOTE: PLEASE NOTE SITUATION WITH(K-38) |
| | OVEN HAS ALSO NOT BEEN ADRESSED??? |
| | SHOWN ON GAS RISER AND AS ELEC ALSO. |
| | IT WAS BROUGHT TO OUR ATTENTION BY |
| | CONTRACTOR THAT DOUBLE OVEN WAS NO |
| | LONGER GAS AND WAS GOING TO BE ONLY |
| | ELECTRIC. THE LAST FOUR TIMES PLANS |
| | HAVE COME IN FOR REVIEW, ALL STILL SHOW |
| | AS GAS AND ELECTRIC???? |
| | PLEASE VERIFY AND MAKE ANY NESS. CHANGES |
| | |
| | 3)NOTE: PLEASE THERE ARE ITEMS ON |
| | KITCHEN EQUIPMENT SCHEDULE THAT DO NOT |
| | CORRELATE CIRCUTI #`S WITH SAME ITEMS |
| | ON PANEL SCHEDULES?? |
| | |
| | 4)NOTE:PLEASE SEE LETTER ATTACHED; |
| | PLEASE NOTE A FOUR TIMES FEE HAS BEEN |
| | ADDED FOR PLAN REVIEW PORTION OF PERMIT |
| | FEE. THIS IS REQ`D UNDER FAC.553.80(2)B |
| | PLEASE SEE ATTACHED BZ RECEIPT. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL, OR IF A MEETING IS NEEDED |
| | TO GO OVER PLANS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |