| Plan Review Notes For Permit 02061083 |
| Permit Number |
02061083 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-10-29 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE, LAST REVISION HAD | | | A PROVISO THAT THE DOUBLE OVEN (K-38) | | | WAS CHANGING FROM GAS TO ELECTRIC? | | | PLEASE NOTE PLANS STILL SHOW AS GAS ON | | | ELECTRICAL PLANS AND GASRISER. | | | PLEASE CLARIFY. | | | | | | 2)NOTE: LAST SET OF PLANS WERE REDLINED | | | FOR SIGN CIRCUIT REQ`D TO BE DEDICATED. | | | PLEASE NOTE PANEL SCHEDULE STILL SHOWS | | | W/ SHOW WINDOW RECEPTS. PLEASE CORRECT | | | 600-5 | | | | | | 3)NOTE; PLEASE NOTE, RISER DIAGRAM | | | AND PANEL SCHEDULES DO NOT CORRELATE. | | | PLEASE NOTE OCP SHOWN ON M1 TO FEED | | | T-TX-1, DOES NOT CORRELATE W/ RISER. | | | PLEASE ALSO NOTE PANEL "BRW3" DOES NOT | | | SHOW A FEED/OCP TO TRASNFORMER TX-2? | | | PLEASE CLARIFY TX-2 SHOWN ON PANEL | | | M2?? | | | | | | PLEASE CORRELATE PLANS AND SUBMIT FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|