| 2002-08-30 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | | | | 1) FROM PREVIOUS REVIEW, COMMENT #7 MAN- | | | UFACTURE CUT SHEET NOT FOUND. PLEASE | | | SUBMIT INFORMATION FOR REVIEW. | | | 2) FROM PREVIOUS REVIEW#12(B) SUBMIT | | | MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT | | | TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND THE FBC-2001 FUEL GAS | | | CODE SECTION 402.2-AND-#12(C) | | | MANUAL SHUT OFF VALVE TO BE UPSTREAM OF | | | AUTOMATIC SHUT OFF VALVE WITH A UNION | | | IN BETWEEN FOR SERVICE OF SOLINOID VALVE | | | (NOT SHOWN ON RISER). | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|