Plan Review Notes
Plan Review Notes For Permit 02061083
Permit Number 02061083
Review Stop P
Sequence Number 2
Notes
Date Text
2002-08-30 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) FROM PREVIOUS REVIEW, COMMENT #7 MAN-
 UFACTURE CUT SHEET NOT FOUND. PLEASE
 SUBMIT INFORMATION FOR REVIEW.
 2) FROM PREVIOUS REVIEW#12(B) SUBMIT
 MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT
 TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND THE FBC-2001 FUEL GAS
 CODE SECTION 402.2-AND-#12(C)
 MANUAL SHUT OFF VALVE TO BE UPSTREAM OF
 AUTOMATIC SHUT OFF VALVE WITH A UNION
 IN BETWEEN FOR SERVICE OF SOLINOID VALVE
 (NOT SHOWN ON RISER).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377