| Plan Review Notes For Permit 02061083 |
| Permit Number |
02061083 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-09-03 00:00:00 | PROVISO: | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPRESSION, & WALK-IN COOLERS. | | | PLEASE PROVIDE PLANS & MANUFACTURER | | | SUBMITTAL DATA WITH PERMIT APPLICATION. | | | | | | PLEASE NOTE: | | | | | | EXHAUST FANS FOR HOOD/GREASE DUCT SHALL | | | TERMINATE: | | | | | | (A) A MINIMUM OF 10 FT FROM ADJACENT | | | BUILDINGS, PROPERTY LINES & AIR INTAKES. | | | | | | (B) TERMINATE A MINIMUM OF 40" ABOVE THE | | | THE ROOF SURFACE. | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR AS | | | PER 2001 FBC(M) 606.2.2 IN ACCORDANCE | | | WITH 606.4 OR 606.4.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|