| 2002-08-29 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 02061083 | | | ADD: 700 S ROSEMARY B-19 | | | CONT: SHAKMAN | | | TEL: (561)750-8288 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1) EXTERIOR DOOR A-001 REQUIRES A 1 1/2 | | | HR RATING, TABLE 705.1.2, SEE NOTE 2. | | | | | | 2) SHEET A-5.01 WALL DETAIL INDOCATES | | | THE USE OF ELEVATED BOOTHS: | | | 11-4.1.3(1) AT LEAST ONE ACCESSIBLE | | | ROUTTE COMPLYING WITH 11-4.3 SHALL | | | CONNECT ACCESSIBLE BUILDING OR FACILITY | | | ENETRANCES WITH ALL ACCESSIBLE SPACES | | | AND ELEMENTS WITHIN THE BUILDING OR | | | FACILITY. PROVIDE INFORMATION HOW YOU | | | WILL COMPLY WITH THIS SECTION! PROVIDE | | | PRODUCT INFO. FOR LIFT, ETC ... | | | | | | 3) INDICATE ON PLANS COMPLIANCE WITH | | | 403.2.4.1 PERMANENT PLATFORMS MAY BE | | | CONSTRUCTED OF "FIRE RETARDANT TREATED | | | WOOD" FOR TYPE I, II III OR IV CONSTRUC- | | | TION. | | | | | | 4) REMOVE ALL OLD PAGES FROM PLAN, RESUB | | | WITH ONLY 1OLD SET OF PLANS WITH CORREC- | | | TIONS!!!!! | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096 X 8412 |
|