Plan Review Notes
Plan Review Notes For Permit 02061083
Permit Number 02061083
Review Stop P
Sequence Number 1
Notes
Date Text
2002-07-18 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) PLEASE SUBMIT A GREASE WASTE RISER
 DIAGRAM.
 2) PLEASE SUBMIT A WATER RISER DIAGRAM
 FOR KITCHEN AND BAR AREAS. WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIX-
 TURES IN AN "EFFECTIVE RANGE" NOT AT TOP
 OF DROPS AS SHOWN ON SHT P-400 BATHROOM
 WATER ISOMETRIC.PLEASE CHANGE WATER
 HAMMER ARRESTOR LOCTIONS ON BATHROOM
 WATER RISER DIAGRAM. PDI-WH 201 SECTION
 604.9
 3) PLEASE SEE PLUMBING REVIEW COMMENTS
 FOR PERMIT #02061076 CONCERNING TOILET
 ROOM ELEVATIONS.
 4) SHT P4 FOOD SERVICE EQUIP. SHTS. P5
 REFERS TO SAFE WASTE. SAFE WASTE NOT
 APPROVED. INDIRECT WASTE REQUIRED.
 5) SHT P4 FOOD SERVICE EQUIP. SHEETS,
 ALL INDIRECT WASTE SHALL DRAIN TO FLOOR
 SINKS. P6 REFERS TO 2" STUB UP 4" ABOVE
 FLOOR. SECTION 802.3 APPROVED INDIRECT
 WASTE RECEPTOR.
 6) SHT P-000 PLUMBING SPECIFICATIONS,
 #'S 1.2, 1.7, & 6.1 REFER TO STANDARD
 BUILDING CODE. CODE IN EFFECT IS FBC-
 2001 PLUMBING & FBC-2001 FUEL GAS PLEASE
 CHANGE CODE REFERENCE.
 7) SHT P-000 PLMBG. SPECS. # 2.6 FILTER
 SHALL BE NSF APPROVED. PLEASE SUBMIT
 MANUF. INFOR. FOR FILTER.
 8) SHT P-000 PLMG. SPECS., # 1.8, DI-
 ELECTRIC UNIONS NOT APPROVED FOR WATER
 PIPING. PLEASE DELETE REFERENCE.
 9) SHT P-000 GAS WATER HEATER AND STOR-
 AGE TANK DETAIL. FLOOR SINK REQUIRED FOR
 ALL INDIRECT WASTE FROM PRESSURE/TEMP
 RELIEF VALVE DISCHARGE AND PAN DRAIN.
 PAN DRAIN REQUIRED FOR ALL WATER HEATERS
 AND STORAGE TANKS ABOVE THE GROUND FLOOR
 SPACE. SEC 504.8.1" PAN DRAIN REQUIRED
 SEC 623.7 FUEL GAS
 10) SHT P-000 PLUMBING NOTES #5 - SEE
 PLAN REVIEW COMMENT # 4 SAFE WASTE.
 11) PER UTILITY ORDINANCE, DRAINAGE FROM
 DISHWASHER SHALL DRAIN INTO SANITARY
 SYSTEM NOT INTO GREASE WASTE SYSTEM.
 12) THE FOLLOWING INFORMATION IS REQUIR-
 ED FOR GAS PERMIT.
 A. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU 402
 (34). NO BTU'S SHOWN FOR WATER HEATER &
 STORAGE TANK.
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
 C. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377