| 2002-07-18 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | |
| | 1) PLEASE SUBMIT A GREASE WASTE RISER |
| | DIAGRAM. |
| | 2) PLEASE SUBMIT A WATER RISER DIAGRAM |
| | FOR KITCHEN AND BAR AREAS. WATER HAMMER |
| | ARRESTORS SHALL BE LOCATED NEAR THE FIX- |
| | TURES IN AN "EFFECTIVE RANGE" NOT AT TOP |
| | OF DROPS AS SHOWN ON SHT P-400 BATHROOM |
| | WATER ISOMETRIC.PLEASE CHANGE WATER |
| | HAMMER ARRESTOR LOCTIONS ON BATHROOM |
| | WATER RISER DIAGRAM. PDI-WH 201 SECTION |
| | 604.9 |
| | 3) PLEASE SEE PLUMBING REVIEW COMMENTS |
| | FOR PERMIT #02061076 CONCERNING TOILET |
| | ROOM ELEVATIONS. |
| | 4) SHT P4 FOOD SERVICE EQUIP. SHTS. P5 |
| | REFERS TO SAFE WASTE. SAFE WASTE NOT |
| | APPROVED. INDIRECT WASTE REQUIRED. |
| | 5) SHT P4 FOOD SERVICE EQUIP. SHEETS, |
| | ALL INDIRECT WASTE SHALL DRAIN TO FLOOR |
| | SINKS. P6 REFERS TO 2" STUB UP 4" ABOVE |
| | FLOOR. SECTION 802.3 APPROVED INDIRECT |
| | WASTE RECEPTOR. |
| | 6) SHT P-000 PLUMBING SPECIFICATIONS, |
| | #'S 1.2, 1.7, & 6.1 REFER TO STANDARD |
| | BUILDING CODE. CODE IN EFFECT IS FBC- |
| | 2001 PLUMBING & FBC-2001 FUEL GAS PLEASE |
| | CHANGE CODE REFERENCE. |
| | 7) SHT P-000 PLMBG. SPECS. # 2.6 FILTER |
| | SHALL BE NSF APPROVED. PLEASE SUBMIT |
| | MANUF. INFOR. FOR FILTER. |
| | 8) SHT P-000 PLMG. SPECS., # 1.8, DI- |
| | ELECTRIC UNIONS NOT APPROVED FOR WATER |
| | PIPING. PLEASE DELETE REFERENCE. |
| | 9) SHT P-000 GAS WATER HEATER AND STOR- |
| | AGE TANK DETAIL. FLOOR SINK REQUIRED FOR |
| | ALL INDIRECT WASTE FROM PRESSURE/TEMP |
| | RELIEF VALVE DISCHARGE AND PAN DRAIN. |
| | PAN DRAIN REQUIRED FOR ALL WATER HEATERS |
| | AND STORAGE TANKS ABOVE THE GROUND FLOOR |
| | SPACE. SEC 504.8.1" PAN DRAIN REQUIRED |
| | SEC 623.7 FUEL GAS |
| | 10) SHT P-000 PLUMBING NOTES #5 - SEE |
| | PLAN REVIEW COMMENT # 4 SAFE WASTE. |
| | 11) PER UTILITY ORDINANCE, DRAINAGE FROM |
| | DISHWASHER SHALL DRAIN INTO SANITARY |
| | SYSTEM NOT INTO GREASE WASTE SYSTEM. |
| | 12) THE FOLLOWING INFORMATION IS REQUIR- |
| | ED FOR GAS PERMIT. |
| | A. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU 402 |
| | (34). NO BTU'S SHOWN FOR WATER HEATER & |
| | STORAGE TANK. |
| | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2. |
| | C. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |