| Plan Review Notes For Permit 02061083 |
| Permit Number |
02061083 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-24 00:00:00 | | | | 1.PROVIDED ADDITIONAL INFORMATION FOR | | | THE MECHANICAL EQUIPMENT AT THE | | | MEZZANINE LEVEL. IS THIS AREA RATED? | | | INDICATE ACCESS. INDICATE IF ROOM IS | | | VENTILATED. | | | | | | 2.PLEASE NOTE, BALANCED RETURN AIR - | | | 2001 FBC(M) 601.4 RETURN AIR SHALL | | | BE EQUAL TO SUPPLY AIR BY MEANS OF | | | AIR TRANSFER OR A DUCTED RETURN. | | | | | | 3.PLAN SHEET M-201 INDICATES A GLYCOL | | | CHILLER AND CU-1.WILL THIS BE A | | | PART OF PERMIT 02061076?IS THIS | | | LOCATION A PART OF THIS TENANT | | | SPACE? | | | | | | PLEASE NOTE, ADDITIONAL PERMITS REQUIRED | | | FOR WALK-IN COOLERS & FREEZERS, HOOD & | | | FIRE SUPRESSION.PLEASE PROVIDE PLANS | | | & MANUFACTURER INSTALLATION INTRUCTIONS. | | | THIS ALSO INCLUDES ANY DUCT WRAP THAT | | | MAY BE USED ON THE GREASE DUCT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|