| 2002-07-03 00:00:00 | 1) PANIC HARDWARE REQUIRED ON ALL EXIT |
| | DOORS SUBJECT TO OCCUPANCY OF 100 OR |
| | MORE PERSONS. |
| | |
| | 2) OCCUPANT LOAD TO BE DETERMINED BY |
| | FIRE RESCUE. |
| | |
| | 3) TABLES AND CHAIRS APPEAR TO BE TOO |
| | CLOSE TOGETHER IS SOME LOCATIONS. |
| | |
| | 4) PLEASE EXPLAIN OCCUPANT LOAD OF 380 |
| | PERSONS. A REVIEW OF THE SEATING PLAN |
| | DOES NOT INDICATE 380 SEATS. PLEASE |
| | ADVISE. DO THE LARGE SQUARES ON THE |
| | PLANS REPRESENT BOOTHS AND IF SO HOW |
| | MANY TO EACH SQUARE. |
| | |
| | 5) PLEASE PROVIDE DIMENSIONS BETWEEN |
| | CHAIRS. |
| | |
| | 6) PLEASE INDICATE ON THE PLANS THE |
| | LOCATIONS FOR SEATING FOR AT LEAST |
| | TWO HANDICAPPED PERSONS. |
| | |
| | 7) PLEASE PROVIDE FLAME SPREAD FOR |
| | WALLS AND CEILINGS, ESPECIALLY THE |
| | WOOD CEILING. |
| | |
| | 8) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR HOOD, DUCT, AND FIRE SUPPRESSION |
| | SYSTEMS. |
| | |
| | 9) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE SPRINKLER REMODEL. |
| | |
| | 10) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE ALARM SYSTEM REMODEL. |
| | |
| | 11) RAISED PLATFORMS IF PERMANANT MUST |
| | BE THE SAME TYPE OF CONSTRUCTION AS THE |
| | BUILDING. |
| | |
| | 12) OPEN FLAME DEVICES ARE NOT ALLOWED. |
| | GAS LIGHTS AND CANDLES MAY ONLY BE |
| | USED IF THE EXCEPTIONS OF THE CODE CAN |
| | BE MET. |
| | |
| | 13) NO FIRE SPRINKLER PLANS PROVIDED |
| | WITH DRAWINGS. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |