2002-07-15 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE CLARIFY GROUNDING FOR
 TRANSFORMERS PER 250-30
  
 2)NOTE: PLEASE CLARIFY TEMPORARY OCP FOR
 #3 CONDUCTORS FEEDING "M2".
 SHOWS 600A
  
 3)NOTE: PLEASE NOTE THAT A DISC IS SHOWN
 ON RISER DIAGRAM AFTER "TX-1" TO MEET
 240-21. PLEASE CLARIFY LOCATION OF THIS
 DISC ON PLANS?? NOT SHOWN ON E-4.02
 PLEASE NOTE CLEARENCES FOR EQUIPMENT
 ON MEZZ/STORAGE FOR DEDICATED ELECTRICAL
 SPACE PER 110-26.
  
 4)NOTE: PLEASE CLARIFY MISSING GFI FOR
 ROOF TOP A/C EQUIPMENT PER 210-63. IS
 THIS EXISTING?
  
 5)NOTE: PLEASE NOTE THAT NOTE ON E-4.01
 MENTIONS ALL RECEPTS WITHIN 2' OF WET
 AREAS ARE TO BE GFI. PLEASE NOTE THAT
 PER LOCAL AMENDMENTS ALL RECEPTS W/IN
 6' OF SINKS/WET AREAS ARE TO BE GFI/GFI
 PROETCTED. 210-8
  
 6)NOTE: PLEASE CLARIFY LOCATION OF SIGN
 CIRCUIT PER 600-5
  
 7)NOTE: PLEASE CLARIFY LOCATION OF SHOW
 WINDOW OUTLETS PER 210-62.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  