Plan Review Notes For Permit 02061083
Permit Number 02061083
Review Stop B
Sequence Number 1
Notes
Date Text
2002-07-30 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT:02061083
 ADD: 700 S ROSEMARY AV #212
 CONT: SHAKMAN CONSTRUCTION
 TEL: (561)750-8288
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) TOTAL OCCUPANT LOAD GIVEN 413, VS
 TABLE 103.1 CALCULATION @ 510.
  
 2) PLANS STATE THAT 3 EXIT DOORS ARE
 AVAILABLE, SEC 1001.1.3 STATES THAT
 MEANS OF EGRESS SHALL NOT BE PERMITTED
 THROUGH KITHENS OR RESTROOMS, ONLY (2)
 EXITS EXIST.
  
 3) MAXIMUM OCCUPANT LOAD FOR THE (2)
 EXITS, 34"X3=102"/.2= 510 PERSONS,
 MAXIMUM.
  
 4) TABLE 704.1, OCCUPANCY SEPERATION
 REQUIES 2HRS., NO INFO GIVEN FOR DOOR
 OPENING A-001 REQUIRES 1 1/2 HR. PROTEC-
 TION, SEE TABLE 705.1.2.
  
 5) 1019.7 (1-2) PANIC HARDWARE REQUIRED
 FOR A-2 > 300 PERSONS.
  
 6) COOLER DOOR VS CORRIDOR 012:
 DURING ITS SWING, ANY DOOR IN A MEANS OF
 EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST
 ONE HALF OF THE REQUIRED WIDTH OF THE
 AISLE, CORRIDOR, PASSAGEWAY OR LANDING,
 NOR PROJECT MORE THAN 7" INTO THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR OR
 LANDING WHEN FULLY OPEN.
  
 7) SEC 1019.8.1.IN BUILDING OF A GROUP A
 OCCUPANCY, FLIGHTS OF LESS THAN 3 RISERS
 SHALL NOT BE USED IN INTERIOR OR EXTER-
 IOR STAIRWAYS, EXIT PASSAGEWAYS, AILES,
 AT ENTRANCE OR ELSEWHWHERE IN CONNECTION
 WITH REQUIRED EXITS.
  
 8)11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY.
  
 9)11-4.1.3(3) GROUND & FLOOR SURFACES
 ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE
 ROOMS & SPACES SHALL COMPLY WITH
 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE)
 A STATIC COEFFICIENT OF FRICTION OF 0.6
 IS RECOMENDED FOR ACCESSIBLE ROUTES
 AND 0.8 FOR RAMPS.
  
 10) 11-5.2 COUNTERS & BARS, 11-5.4
 DINING AREAS, INDICATE CODE COMPLIANCE.
  
 11) 1016.1.1MEANS OF EGRESS ILLUMINATION
 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH THIS SECTION
 FOR EVERY BUILDING AND STRUCTURE.FOR THE
 PURPOSE OF THIS REQUIREMENT, EXIT ACCESS
 SHALL INCLUDE STAIRS, AILES, CORRIDORS
 RAMPS, AND EXIT PASSAGEWAYS LEADING TO A
 PUBLIC WAY.
  
 12) 1016.1.3 THE FLOORS AND OTHER WALK-
 ING SURFACES WITHIN AN EXIT AND WITHIN
 THE PORTIONS OF THE EXIT ACCESS AND EXIT
 DISCHARGE DESIGNATED IN 1016.1.1 SHALL
 BE ILLUMINATED TO VALUES OF AT LEAST
 1-FT CANDLE MEASURED AT THE FLOOR.
  
 13) EMERGENCY LIGHTING AND STANDBY POWER
 1016.2.1 FOR THE PURPOSE OF THIS REQUIRE
 MENT EXIT ACCESS SHALL INCLUDE DESIGNAT-
 ED STAIRS, AISLES,RAMPS & CORRIDORS.
 PROVIDE INFO.
  
 14) STAGES & PLATFORMS, LOADS: 403.2.3.1
 THE DESIGN OF PLATFORMS SHALL COMPLY
 WITH THE REQUIREMENTS OF CHAP 16.
 PROVISIONS SHALL BE MADE FOR THE LOADS
 IN 403.2.3.2 AND TABLE 1604.1, LIVE LOAD
  
 15) 403.2.4.1 PERMANENT PLATFORMS MAY
 BE CONSTRUCTED OF "FIRE RETARDANT TREAT-
 ED WOOD"FOR TYPES I, II, III, AND IV
 CONSTRUCTION.
  
 16) WILL THE SPACE BENEATH THE PERMANENT
 PLATFORM BE USED FOR STORAGE OR ANY
 OTHER PURPOSE OTHER THAN EQUIPMENT,
 WIRING OR PLUMBING?
  
 17) SHEET A-5.01 BREWERY WALL DETAIL
 INDICATES AN ELEVATED BOOTH ARRANGEMENT,
 11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY.
  
 18) 1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 19)1511.7ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7.
  
 20) A-3.01 DETAIL MECHANICAL PLATFORM @
 KITHEN, THIS DETAIL, THIS CONSTRUCTION
 OF A MEZZANINE SHALL MEET THE REQUIRE-
 MENTS OF 503.2.3.1-4.
  
 21) INDICATE CODE CONFORMANCE FOR 1 HR
 RATING ON WALLS & FLOOR OF MEZZANINE?
  
 22) INDICATE THE ALLOWABLE SAFE FLOOR
 LOADS OF MEZZANINE, IS EQUIPMENT TO
 SET ON THE FLOOR? OR IS THERE ROOM FOR
 ADDITIONAL STORAGE?
  
 23)106.4.2 STORAGE & FACTORY- INDUS-
 TRIAL OCCUPANCIES. IT SHALL BE THE
 RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY
 WHERE EXCESSIVE FLOOR LOADING IS LIKELY
 TO OCCUR, TO EMPLOY A COMPETENT ARCHI-
 TECT OR ENGINEER IN COMPUTING THE SAFE
 FLOOR LOAD CAPACITY. ALL SUCH COMPUTA-
 TIONS SHALL BE ACCOMPANIED BY AN AFFA-
 DAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE ALLOWABLE FLOOR LOADS
 ON EACH FLOOR IN POUNDS PER SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
  
 ADDITIONAL SQ FT (MEZZANINE) REQUIRES
 REVIEW BY COUNTY FOR POSSIBLE ASSESSMENT
 OF IMPACT FEES.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026