| Plan Review Notes For Permit 02061076 |
| Permit Number |
02061076 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-01-28 00:00:00 | ************ UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE EQUIPMENT SHEDULE | | | AND PANEL SCHEDULE. PLEASE SEE GLYCOL | | | CHILLER, PANEL SHOWS 35A OCP AND EQUIP- | | | -MENT SCHEDULE SHOWS A 45A LOAD?? | | | | | | 2)NOTE; PLEASE SHOW CIRCUIT #'S FOR | | | EMLT/EXT LTS. 700-12E. | | | CLARIFY TYPE OF FIXTURES INSTALLED. | | | | | | 3)NOTE: PLEASECLARIFY "LOCATION" TYPE | | | SHOWN ON PLAN PER NECART:500. PLANS | | | SHOW CLASS 1 DIV 1. PLEASE VERIFY FIELD | | | CONDITIONS AND CHECK ART 500 FOR | | | POSSIBLE OTHER CLASS LOCATION. IT HAS | | | BEEN NOTED BY INSPECTOR THAT WIRING IS | | | NOT PER CLASS 1 DIV 1 AS NOTED ON PLAN?? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|