2003-01-28 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SEE EQUIPMENT SHEDULE
 AND PANEL SCHEDULE. PLEASE SEE GLYCOL
 CHILLER, PANEL SHOWS 35A OCP AND EQUIP-
 -MENT SCHEDULE SHOWS A 45A LOAD??
  
 2)NOTE; PLEASE SHOW CIRCUIT #'S FOR
 EMLT/EXT LTS. 700-12E.
 CLARIFY TYPE OF FIXTURES INSTALLED.
  
 3)NOTE: PLEASECLARIFY "LOCATION" TYPE
 SHOWN ON PLAN PER NECART:500. PLANS
 SHOW CLASS 1 DIV 1. PLEASE VERIFY FIELD
 CONDITIONS AND CHECK ART 500 FOR
 POSSIBLE OTHER CLASS LOCATION. IT HAS
 BEEN NOTED BY INSPECTOR THAT WIRING IS
 NOT PER CLASS 1 DIV 1 AS NOTED ON PLAN??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372