2002-07-03 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW/CLARIFY LOCATIONS
 PER ART 500 NEC. HAZARDOUS LOCATIONS FOR
 GRAIN/MIXING/GRINDING???
  
 2)NOTE: PLEASE CLARIFY AND LABEL TRANS-
 -FORMERS AT THEIR LOCATIONS. PLEASE
 NOTE TRANS. BEING SHOWN IN TWO LOCATIONS
 ??
  
 3)NOTE: PLEASE SEPARATE LINE DIAGRAM FOR
 SERVICES EQUIPMENT BEING INSTALLED UNDER
 THIS PERMIT.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED?
 110-9
  
 5) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
 215-2,215-3,230-42
  
 6) NOTE: PLEASE SHOW CALCULATIONS FOR
 TRACK LIGHTING PER 220-12B.
  
 7)NOTE: PLEASE CLARIFY GROUNDING OF
 TRANSFORMERS PER 250-30
  
 8 )NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS NEED TO BE SHOWN. SQ FT/
 RECEPT LOADS ETC. PER 220-3,220-10,
 220-11, 220-13. (215-5)
 PLEASE CLARIFY ALL SHOWN AT CONNECTED
 LOAD?
  
 9)NOTE: PLEASE CLARIFY OCP FOR TEMP FEED
 TO "M2". PLEASE INDICATE LOCATION OF
 "EXISTING" GUTTER ON SECOND FLR.?
 PLEASE NOTE LENGTH OF TAPPED CONDUCTORS
 PER 240-21. RISER SHOWS 100A #3`S WITH
 A 600A FEED? PLEASE CLARIFY OCP AT
 "M3" SHOWN AS 200A /ALSO NOTE TAPPED
 CONDUCTOR LENGTH? PER 240-21
  
 10)NOTE: PLEASE NOTE THAT REVIEW FOR
 RISER DIAGRAM FOR FUTURE REST. WILL NOT
 BE REVIEWED AT THIS TIME. (NOT COMPLETE)
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  