| Date |
Text |
| 2002-07-03 00:00:00 | ************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SHOW/CLARIFY LOCATIONS |
| | PER ART 500 NEC. HAZARDOUS LOCATIONS FOR |
| | GRAIN/MIXING/GRINDING??? |
| | |
| | 2)NOTE: PLEASE CLARIFY AND LABEL TRANS- |
| | -FORMERS AT THEIR LOCATIONS. PLEASE |
| | NOTE TRANS. BEING SHOWN IN TWO LOCATIONS |
| | ?? |
| | |
| | 3)NOTE: PLEASE SEPARATE LINE DIAGRAM FOR |
| | SERVICES EQUIPMENT BEING INSTALLED UNDER |
| | THIS PERMIT. |
| | |
| | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED? |
| | 110-9 |
| | |
| | 5) NOTE: PLEASE SHOW ALL CONTINUOUS AT |
| | 125%. (LIGHTING ETC) |
| | 215-2,215-3,230-42 |
| | |
| | 6) NOTE: PLEASE SHOW CALCULATIONS FOR |
| | TRACK LIGHTING PER 220-12B. |
| | |
| | 7)NOTE: PLEASE CLARIFY GROUNDING OF |
| | TRANSFORMERS PER 250-30 |
| | |
| | 8 )NOTE: PLEASE NOTE THAT THE LOAD |
| | CALCULATIONS NEED TO BE SHOWN. SQ FT/ |
| | RECEPT LOADS ETC. PER 220-3,220-10, |
| | 220-11, 220-13. (215-5) |
| | PLEASE CLARIFY ALL SHOWN AT CONNECTED |
| | LOAD? |
| | |
| | 9)NOTE: PLEASE CLARIFY OCP FOR TEMP FEED |
| | TO "M2". PLEASE INDICATE LOCATION OF |
| | "EXISTING" GUTTER ON SECOND FLR.? |
| | PLEASE NOTE LENGTH OF TAPPED CONDUCTORS |
| | PER 240-21. RISER SHOWS 100A #3`S WITH |
| | A 600A FEED? PLEASE CLARIFY OCP AT |
| | "M3" SHOWN AS 200A /ALSO NOTE TAPPED |
| | CONDUCTOR LENGTH? PER 240-21 |
| | |
| | 10)NOTE: PLEASE NOTE THAT REVIEW FOR |
| | RISER DIAGRAM FOR FUTURE REST. WILL NOT |
| | BE REVIEWED AT THIS TIME. (NOT COMPLETE) |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |