| Date |
Text |
| 2002-12-02 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 02061040 |
| | ADD: 267 BARCELONA RD |
| | CONT: HOME TECHNICAL SERVIVES |
| | TEL: (561)575-5758 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) 3401.7.1.3 WHERE THE EXISTING BUILD- |
| | ING AND THE ADDITION ARE NOT SEPERATED |
| | BY A FIREWALL AND THE ADDITION IS LESS |
| | THAN 25% OF THE AREA OF THE EXISTING |
| | BUILDING, THE ADDITION SHALL CONFORM TO |
| | ALL REQUIREMENTS OF THIS CODE APPLICABLE |
| | TO THE BUILDING OF THE COMBINED AREA OF |
| | THE EXISTING BUILDING AND ADDITION. |
| | |
| | THE USE OF THE EXISTING WINDOWS ON THE |
| | NEW CONSTRUCTION SHALL REQUIRE SITE |
| | SPECIFIC ENGINEERING.THERE IS 2 REQUIRE- |
| | MENTS TO BE MET, (1) FOR WIND & (2) FOR |
| | LARGE MISSLE IMPACT TESTING. IF SITE |
| | SPECIFIC ENGINEERING ISFOR WIND ONLY THE |
| | LARGE MISSLE REQUIREMENT MUST BE MET |
| | WITH STORM SHUTTERS. |
| | |
| | SITE SPECIFIC ENGINEERING (PRODUCT |
| | APPROVAL) REQUIRES THE WET SIGNATURE, |
| | DATE AND EMBOSSED SEAL OF THE ENGINEER |
| | CERTIFYING THE PRODUCT AND SIGNATURE |
| | AND SEAL OF THE DESIGN PROFESSIONAL |
| | OF RECORD. SEE CITY FORM. |
| | |
| | 2)1606.1.4(1) IN WIND BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| | ASSUMED TO BE OPENINGS UNLESS SUCH |
| | GLAZING IS IMPACT RESISTANT OR PROTECTED |
| | WITH AN IMPACT RESISTANT COVERING MEET- |
| | ING THE REQUIREMENTS OF SSTD 12, ASTM |
| | E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| | 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF |
| | LARGE MISSLE TEST. |
| | FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED. MISSING REPORTS: |
| | A) FRENCH DOORS W/ SIDELITES |
| | B) SINGLE HUNG WINDOW |
| | C) OCTOGON WINDOW ASSUMED (FIXED) |
| | D) STORM SHUTTERS |
| | E) ROOFING ASSEMBLIES |
| | |
| | 3) PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING. |
| | FBC 1606.1.4. |
| | |
| | 4)FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | 5)1503.4.4 PROTECTION AGAINST DECAY & |
| | TERMITES. CONDENSATE LINES & ROOF DOWN |
| | SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| | AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| | TENSIONS, OR SPLASH BLOCKS. SEE SHEET |
| | A-2, ENG 9 & 12. |
| | |
| | 6)905.2.1 RESIDENTIAL SMOKE ALARMS: |
| | NFPA 72.A-8-1.2.1 IN FAMILY UNITS WITH |
| | MORE THAN ONE BEDROOM AREA OR WITH BED- |
| | ROOMS ON MORE THAN ONE FLOOR, MORE THAN |
| | ONE SMOKE DETECTOR IS REQUIRED. |
| | |
| | 7) 905.2.2 WHERE THE DWELLING OR |
| | DWELLING UNIT CONTAINS MORE THAN ONE |
| | STORY, DETECTORS ARE REQUIRED ON EACH |
| | STORY, LOCATED IN CLOSE PROXIMITY TO THE |
| | STAIRWAY LEADING TO THE FLOOR ABOVE. |
| | |
| | 8)1012.5 GROUP R-3 LANDING WIDTH SHALL |
| | BE NO LESS THAN THE DOOR WIDTH IT SERVES |
| | AND THE DEPTH SHALL BE NO LESS THAN 36" |
| | THE LANDING MAY BE ONE STEP LOWER THAN |
| | THE INSIDE FLOOR LEVEL BUT NOT MORE THAN |
| | 7" LOWER. PLANS DO NOT SHOW THE OUTSIDE |
| | STOOP. |
| | |
| | 9)1203.4.2 EVERY TOLIET ROOM SHALL |
| | HAVE WINDOWS AS SPECIFIED FOR HABITABLE |
| | ROOMS PROVIDING IN NO CASE LESS THAN 3 |
| | SQ FT OPEN SPACE, OR HAVE APPROVED EQUIV |
| | ALENT VENTILATION. MECH CODE 402.3.1 |
| | REQUIRES MECHANICAL VENTILATION PER |
| | SEC 403. PRIVATE DWELL/ BATHROOMS, |
| | MECHANICAL EXHAUST CAPACITY OF 50 CFM |
| | INTERMITTTENT OR 20 CFM CONTINUOUS. |
| | |
| | 10)PROVIDE ENERGY CALCULATIONS AND |
| | EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| | AS REQUIRED BY THE 2001 FLORIDA ENERGY |
| | EFFICIENTCY CODE FOR BUILDING CONSTRUC- |
| | TION. FORM 600-C. |
| | |
| | 11)TABLE 2306.1 PALM BEACH COUNTY |
| | AMENDMENTS |
| | ROOF SHEATHING NAILING REQUIREMENTS |
| | < 25' MEAN ROOF HEIGHT |
| | ZONE 1 & 28D COMMON |
| | 6" EDGES & 6" INTERMEDIATES |
| | |
| | ZONE 38DCOMMON |
| | 4" EDGES & 6" INTERMEDIATES |
| | |
| | 12) ENG. TO REVIEW CONNECTOR SCHEDULE, |
| | VALUE ON CONNECTORS (A&E) F1 & F2 ARE |
| | HIGH, (K&L) UPLIFT IS HIGH. 2002 CATOLOG |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | JIM WITMER |
| | PLAN REVIEW |
| | TEL: (561)659-8096 EX.8412 |
| | FAX: (561)659-8026 |