| Date |
Text |
| 2002-07-30 00:00:00 | CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-PERCENTAGE OF OPENINGS AT DINING ROOM |
| | EXCEEDS THE PERCENTAGE ALLOWED BY |
| | TABLE 600 FBC 2001. |
| | 3-STRUCTURAL DRAWINGS SHALL HAVE ALL 5 |
| | ITEMS REQUIRED BY SEC. 1606.1.7 FBC |
| | 4-PROVIDE COMPLETE SECTION/DETAIL THRU |
| | FIREPLACE AND CHIMNEY. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 5-PROVIDE COMPLETE BEAM & LINTEL SCHED. |
| | & CLEARLY IDENTIFY THEM ON PLANS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 6-PROVIDE COMPLETE DETAILS/ SECTIONS AND |
| | SPECS AT FRAMING FOR SLIDING GLASS |
| | DOORS @ LEISURE RM, INCLUDING CORNER. |
| | **NOTE: TAKE INTO CONSIDERATION THE SIZE |
| | OF DOORS AND PRODUCT APPROVAL FOR THIS |
| | TYPE OF INSTALLATION, INCLUDING CORNER |
| | UNION BETWEEN THE TWO ASSEMBLIES. ALSO |
| | HURRICANE MISSILE IMPACT PROTECTION. |
| | 7-CLEARLY INDICATE ON PLANS MASONRY WALL |
| | VERTICAL REINFORCEMENT. SPACING IS NOT |
| | CLEAR. WHY THERE IS NOT REINFORCEMENT |
| | AT THE ENDS OF ALL OPENINGS/. HOW ARE |
| | THE OPENINGS REINFORCED TO RECEIVE THE |
| | HURRICANE MISSILE IMPACT ASSEMBLIES? |
| | **WHY THERE'S ONLY ONE SHEAR BLOCK WALL |
| | ON ENTIRE HOUSE? |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 8-ENGINEER TO INCLUDE HIS LICENSE # AND |
| | TELEPHONE # ON ALL DRAWINGS AS REQ'D |
| | BY CHAPTER 471 FL STATUTES WHEN |
| | SUBMITTING PLANS FOR PUBLIC RECORDS. |
| | 9-PROVIDE AREA TABULATION BREAKDOWN TO |
| | ASSESS VALUE AND RADON FEES. LIST A/C |
| | AREAS, PORCHES, GARAGE ETC. |
| | 10-WHERE ARE PAGES 1 AND 2 OF THE SET OF |
| | DRAWINGS?. |
| | 11-PROVIDE CURRENT DADE COUNTY OR SBCCI |
| | PRODUCT APPROVAL FOR: |
| | A)12' HIGH FIXED WINDOWS AS SHOWN ON |
| | PLANS. ALONG WITH CORRESPONDING VERT. |
| | MULLION. (MISSILE IMPACT) |
| | B)10' HIGH SLIDING GLASS DOORS AS SHOWN |
| | ON PLANS. |
| | C)10' HIGH SLIDING GLASS DOORS WITH |
| | SIDE POCKET ASSEMBLY AS SHOWN ON PLANS |
| | D)ACTUAL DADE COUNTY OR SBCCI PRODUCT |
| | EVALUATION FOR GARAGE DOOR. |
| | E)ROOF RIDGE VENTS. |
| | F)FIREPLACE UL LISTING AND SPECS. |
| | G)EXTERIOR SWING DOORS. EG. GARAGE, ETC. |
| | H)BBQ UL LISTING AND SPECS. |
| | I)SLIDING WINDOWS PRODUCT APPROVAL |
| | SUBMITTED REQUIRES STORM SHUTTERS FOR |
| | INSTALLATIONS BELOW 30'. SEE SHEET #2. |
| | CLARIFY IF PUTTING STORM SHUTTERS OR |
| | PROVIDE DIFFERENT PRODUCT APPROVAL. |
| | J)FRENCH DOORS WITH TRANSOM ABOVE SINGLE |
| | ASSEMBLY AS SHOWN ON PLANS. OR ENG'R |
| | TO PROVIDE HEADER SPECS & CONNECTORS & |
| | ATTACHMENT OF FRENCH DOOR AND TRANSOM |
| | FRAME TO SUCH MULLION TO CREATE A |
| | SINGLE UNIT. |
| | 12-PROVIDE COMPLETE FRAMING DETAILS FOR |
| | ROUND AND ARCHED WINDOWS AT MASONRY |
| | WALL AND FRAMED WALL. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 13-ARCHITECTURAL DRAWINGS DON'T SPECIFY |
| | TYPE OF ROOF TO BE INSTALLED. |
| | 14-PROVIDE UPLIFT CALCULATIONS AT LANAI |
| | COLUMN FOOTERS. SEC. 1606.1.3 FBC 2001 |
| | 15-CLEARLY KEY PLANS THAT PERTAIN TO |
| | THIS HOUSE. DELETE THE OTHERS. |
| | 16-ENERGY CALCULATIONS: |
| | A)REVISE THE UNDER ATTIC AREA. SEE SEC. |
| | 604.1.A.1 CHAPTER 13 FBC 2001. |
| | B)COMPLETE TOP OF FORM; ADDRESS, ETC. |
| | 17-SEE PLANS FOR ADDITIONAL COMMENTS AND |
| | PLEASE, RETURN REVIEWED SET AFTER |
| | CORRECTIONS ARE DONE TO ORIGINAL DWGS |
| | TO EXPEDITE THE REVIEW PROCESS. |