| Plan Review Notes For Permit 02061029 |
| Permit Number |
02061029 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-07-02 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE ANY NECESSARY CHANGES | | | ON THE DRAWING AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE SUBMIT LOAD CALCAULATION | | | -S.PER 220,215-5. | | | | | | 3} SUBMIT A RISER DIAGRAM INDICATING ALL | | | SERVICE EQUIPMENT AMPERAGE | | | RATINGS,RISER CONDUIT & WIRE SIZES AND | | | GROUNDING SYSTEM USED WITH GEC SIZE. | | | | | | 4} PLEASE SHOW GARAGE RECEPTACLES PER | | | 210-8 ON PLANS. | | | | | | 5} SHOW SERVICE EQUIPMENT LOCATION ON | | | PLANS. | | | | | | 6} PLEASE SHOW ALL A/C EQUIPMENT | | | LOCATIONS ON ELECTRICAL | | | DRAWINGS,AHU'S,CONDENSERS AND | | | DISCONNECTS. | | | | | | 7} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE. PER 210-12 | | | | | | 8} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 9} PLEASE NOTE KITCHEN COUNTER- | | | SPACE RECEPTACLES TO BE GFI PER | | | 210-8(A)(6). NOTE SAME ON PLANS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|