| Plan Review Notes For Permit 02061018 |
| Permit Number |
02061018 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-24 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION MAKE ANY NECESSARY CHANGES | | | ON THE PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE. PER 210-12 | | | | | | 2} THERE ARE 3#6'S AND 1#4 SHOWN AS | | | FEEDERS FOR A/C DISCONNECTS,PLEASE NOTE | | | IF THESE ARE ON THE APPROVED PLANS THEY | | | MUST BE INSTALLED. | | | | | | 3} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 4} SMALL APPLIANCE CIRCUITS,RANGE,WATER | | | HEATERS,CLOTHES DRYER AND AIR HANDLERS | | | SHOWN ON IN LOAD CALCULATIONS DO NOT | | | CORRELATE WITH THE PANEL SCHEDULE. | | | | | | 5} NO WASHER SHOWN ON THE PANEL SCHEDULE | | | | | | 6} ONLY ONE WATER HEATER SHOWN ON THE | | | PANEL SCHEDULE,TWO IN THE CALCS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL; | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|