Plan Review Notes
Plan Review Notes For Permit 02061018
Permit Number 02061018
Review Stop E
Sequence Number 1
Notes
Date Text
2002-06-24 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION MAKE ANY NECESSARY CHANGES
 ON THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 2} THERE ARE 3#6'S AND 1#4 SHOWN AS
 FEEDERS FOR A/C DISCONNECTS,PLEASE NOTE
 IF THESE ARE ON THE APPROVED PLANS THEY
 MUST BE INSTALLED.
  
 3} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4} SMALL APPLIANCE CIRCUITS,RANGE,WATER
 HEATERS,CLOTHES DRYER AND AIR HANDLERS
 SHOWN ON IN LOAD CALCULATIONS DO NOT
 CORRELATE WITH THE PANEL SCHEDULE.
  
 5} NO WASHER SHOWN ON THE PANEL SCHEDULE
  
 6} ONLY ONE WATER HEATER SHOWN ON THE
 PANEL SCHEDULE,TWO IN THE CALCS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392