| Plan Review Notes For Permit 02061002 |
| Permit Number |
02061002 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-26 00:00:00 | *********** UNSAT ************** | | | | | | 1)NOTE: PLEASE CLARIFYGROUPING OF | | | MAINS PER 230-72. PLEASE NOTE FEED IN | | | FROM GEN IS NOT GROUPED WITH OTHER MAINS | | | OF BLDG. PLEASE ALSO NOTE THAT SHUNT | | | TRIPS ARE CONSIDERED MEANS OF DISC. PER | | | 230-76/230-79. | | | | | | 2)NOTE: PLEASE CLARIFY GROUNDING OF | | | GEN. 250 | | | | | | 3)NOTE: PLEASE CLARIFY WHERE CONTINUOUS | | | LOADS ARE SHOWN AT 125%. 215-2/3,230-42 | | | ETC. | | | | | | 4)NOTE: PLEASE NOTE THAT PLANS ARE NOT | | | SIGNED, DATED OR SEALED BY THE ENGINEER | | | OF RECORD PER FS/FAC 471.025. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|