Plan Review Notes
Plan Review Notes For Permit 02060963
Permit Number 02060963
Review Stop B
Sequence Number 1
Notes
Date Text
2002-08-06 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02060963
 ADD: 1920 EMBASSY DRIVE
 CONT: O/B ROBINSON, FELISA
 TEL: (561)689-1536
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) 1007.8.2 SPIRAL STAIRS: PROVIDE THE
 MANUFACTURERS SPECIFICATIONS, THERE IS
 NO DETAIL, FOUNDATION PROVIDED FOR SPIR-
 AL STAIRWAY.
  
 2) SHEET 4OF 6 DETAILS 104.2.1.3
 QUALITY OF BUILDING PLANS, TO BE DRAFTS-
 MAN QUALITY.
  
 3) BALCONY GAURDRAIL, 1015.2 HEIGHT NOT
 LESS THAN 42", (EXTERIOR OF BUILDING).
  
 4) BALCONY GUARDRAIL 1015.3 THE BOTTOM
 RAIL NOT TO ALLOW A 2" SPHERE TO PASS
 THROUGH.
  
 5) BALCONY GAURDRAIL 1015.3 STRENGTH,
 DURABILITY & ATTACHMENT. CONSTRUCTION OF
 GUARDRAILS SHALL BE ADEQUATE IN STRENGTH
 AND DURABILITY AND ATTACHMENT FOR THEIR
 PURPOSE AS DESCRIBED IN 1608.2. GUARD-
 RAIL SYSTEMS SHALL BE DESIGNED & CON-
 STRUCTED FOR A CONCENTRATED 200LB LOAD
 APPLIED AT ANY POINT AND IN ANY DIREC-
 TION AT THE TOP OF THE GUARDRAIL.
  
 6)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
 DISCREPANCY ENERGY CALC R=19.0 VS
 PLAN OF R=32?
  
 7)1503.4 ROOF DRAINS UNLESS ROOFS ARE
 SLOPED TO DRAIN OVER THE ROOF EDGE, ROOF
 DRAINS SHALL BE INSTALLED AT THE LOWEST
 POINT OF THE ROOF. WHERE REQUIRED FOR
 ROOF DRAINAGE,SCUPPERS SHALL BE LOCATED
 AS DETERMINED BY THE ROOF SLOPE AND CON-
 TRIBUTING ROOF AREA. PLANS DO NOT INDI-
 CATE IF THERE IS ANY SLOPE?
  
 8)1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 9)1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 10)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS:
 A) FRENCH DOORS
 B) SLIDING DOORS
 C) SWING DOOR
 D) ROOFING ASSEMBLIES,FLAT & SHINGLES
 E) STORM SHUTTERS SEE SCHEDULE & KEY
 PLAN.
  
 11)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 11) 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 12) 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 13)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
  
 14)FL BLD CODE 2309.6 ATTIC ACCESS, PRO-
 VIDE ATTIC ACCESS 20"X36".
  
 15) GIVE THE LIVE LOADS TRUSSES ARE TO
 BE DESIGNED TO, ALL ROOMS 40 LBS SEE
 TABLE 1604.1
  
 16) TRUSS/ GIRDER LOADS, VERTICAL,
 HORIZONTAL & GRAVITY LOADS,NOT INDICATED
  
 17) 2309.7 VENTILATION FOR ATTIC SPACE.
  
 18) INDICATE SECTIONS SHEET D-1 WHERE IS
 THE CHIMNEY DORMER DETAIL TO BE USED?
 ELEVATIONS DO NOT INDICATE ARCHED OPEN-
 INGS?
  
 424.2.17.9 INDICATE ON THE ADDITION COM-
 PLIANCE WITH POOL SAFETY ACT?
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026