| Date |
Text |
| 2002-07-31 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 02060943 |
| | ADD: 7719 S. DIXIE HWY. |
| | CONT: CMB CONSTUCTION GROUP |
| | TEL: (954)384-7373 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | *****SECOND REVIEW***** |
| | |
| | PALM BEACH MARITINE CHARTER SCHOOL |
| | |
| | 1)11-4.1.3(3) GROUND & FLOOR SURFACES |
| | ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE |
| | ROOMS & SPACES SHALL COMPLY WITH |
| | 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE) |
| | A STATIC COEFFICIENT OF FRICTION OF 0.6 |
| | IS RECOMENDED FOR ACCESSIBLE ROUTES |
| | AND 0.8 FOR RAMPS. |
| | THIS COMMENT WAS#3 FROM FIRST |
| | REVIEW. THIS IS FOR ALL ACCESSIBLE ROOMS |
| | AND SPACES. THE FL ACCESSIBILITY CODE |
| | STATES THAT THE FLOORS ARE TO BE A |
| | STABLE, FIRM, SLIP RESISTANT. THIS DOES |
| | LEAVE ROOM TO INTERPETATION, HOWEVER |
| | ADDAAG 4.5.1 (GUIDELINE) DOES GIVE THE |
| | RANGE OF WHAT IS ACCEPTED, WE PUT THIS |
| | IN AS PART OF A PLAN REVIEW TO COVER |
| | SAFETY ISSUES. VARIOUS FLOORING MATER- |
| | IALS DO HAVE DIFFERENT DEGREES OF SLIP |
| | RESISTANCE. IT HELPS TO PROTECT ALL IN- |
| | VOLVED, DESIGN PROFESSIOALS, CONTRACTORS |
| | AS WELL AS THE END USERS (LAWSUITS). |
| | |
| | 2) MEZZANINE VS OCCUPANCY SEPERATION, |
| | 704.1.2.2(4) DOES ALLOW FOR STORAGE FOR |
| | NONHAZARDOUS MATERIALS FOR GROUP E OCCU- |
| | PANCY WHEN THE AGGREGATE AREA DOES NOT |
| | EXCEED 1/3 THE MAJOR OCCUPANCY. |
| | THE SECOND ISSUE IS STORAGE OCCUPANCY |
| | FOR THE MEZZANINE. SECTION 1027 |
| | DEALS WITH STORAGE SINGLE MEANS OF |
| | EGRESS.THE CODE DOES ALLOW FOR STORAGE |
| | MAXIMUM ONE STORY, FLOOR AREA NOT EXCEED |
| | ING 2500 SQ FT, THIS PROJECT MEETS THESE |
| | (2) CRITERIA. THE THIRD IS TRAVEL DIS- |
| | TANCE NOT TO EXCEED 50 FT. |
| | FURTHEST POINT IS APPROX 76 FT. |
| | THE THIRD ISSUE IS AN ENCLOSED MEZZA- |
| | NINE, ENCLOSED MEANS THE AREA UNDER THE |
| | MEZZANINE. |
| | WHEN THE AREA WITHIN THE MEZZANINE IS |
| | ENCLOSED, IT CONSTITUTES A 2ND STORY. |
| | WHEN DISSCUSSING THE ISSUES ABOVE WITH |
| | THE ASSISTANT BUILD OFF WILLIAM STAPLES |
| | & BUILD OFFICIAL NEIL MELICK THE ONLY |
| | WAY AROUND THIS IS TO ADD A 2ND STAIRWAY |
| | EITHER INTERIOR OR EXTERIOR. THE SECOND |
| | ISSUE IS THIS SPACE WOULD HAVE EXTERIOR |
| | ENTRY WHICH COULD BE SUBLET. THIS WOULD |
| | REQUIRE A 2 HR RATING IF OTHER OCCUPAN- |
| | CIES WERE TO OCCUPY THIS SPACE. |
| | IF THIS SPACE IS USED FOR ANY REASON |
| | OTHER THAN STORAGE VERTICAL ACCESSIBIL- |
| | ITY SHALL BE ADDRESSED. |
| | A DECISION NEEDS TO BE MADE, IF THE |
| | SCHOOL IS TO USE THIS SPACE THE BUILD |
| | OFFICIAL WILL PROVISO THIS ISSUE, AGREE- |
| | ING THAT A SECOND STAIR WILL BE PROVIDED |
| | BEFORE C.O. |
| | |
| | 3) EXTERIOR DOOR# 42 UNDER EXTERIOR |
| | STAIRWAY REQUIRES 1 HR RATING. SEE ATACH |
| | MENT. LIFE SAFETY CODE 3 STORIESAND MORE |
| | 1 1/2 HR. |
| | |
| | 4) FRONT ENTRY DOORS AND SIDELIGHTS, |
| | MISSING PRODUCT APPROVAL REPORTS. SUBMIT |
| | EITHER SBCCI OR DADE COUNTY PRODUCT |
| | TESTING REPORTS.PLANS CALL OUT FOR NEW |
| | DOORS AND SIDELIGHTS. PLANS INDICATE |
| | TRANSOMS, IF PRODUCT TESTING REPORT WAS |
| | NOT TESTED THIS WAY, A SEPERATE REPORT |
| | FOR TRANSOMS SHALL BE REQUIRED. A REPORT |
| | WOULD ALSO BE REQUIRED FOR HORIZONTAL |
| | MULLIONS. |
| | |
| | 5) SITE SPECIFIC ENGINEERING IS FOR |
| | GLAZED OPENINGS THAT HAVE NOT RECEIVED |
| | PRODUCT TESTING FROM A NATIONALLY |
| | RECOGNIZED AGENCY. THIS ALLOWS VENDORS |
| | TO USE PRODUCTS YET NOT TESTED. THE |
| | ENGINEER FOR THE MANUFACTURER SEALS A |
| | SITE SPECIFIC FORM, THE ARCHETECT OF |
| | RECORD SEALS AN AFFIDAVIT THAT THIS |
| | PRODUCT SHALL MEET THE WIND LOADS |
| | IMPOSED IN THIS STRUCTURE. THIS IS NOT |
| | SHOP DRAWINGS. SHOP DRAWINGS SHOULD BE |
| | REVIEWED BY THE DESIGNER OF RECORD, FOR |
| | HIS APPROVAL, AS IS OR RED LINED APPROV- |
| | ED WITH CORRECTIONS OR DENIED. |
| | |
| | 6) THE ISSUE OF EXISTING STORM PANELS, |
| | IF USING THE EXISSTING SHUTTER SYSTEM |
| | THAT WILL BE FINE. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT CAN BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH CO.,THE PERMIT PLANS STAMPED BY |
| | THEM AND THE RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | JIM WITMER |
| | PLAN REVIEW |
| | TEL: (561)659-8096 EX.8412 |
| | FAX: (561)659-8026 |