| 2002-07-06 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | |
| | 1) SHT D1.0 ALL PLUMBING LINES CAPPED |
| | FOR DEMO SHALL BE INSPECTED BEFORE COVER |
| | ING. |
| | 2) SHTS A2.0 & A7.0 ENLARGED TOILET |
| | FLOOR PLAN, SHOW 5' TURNING RADIUS FOR |
| | BOYS AND GIRLS TOILET ROOMS. |
| | 3) SHTS A2.0 & A7.0 ENLARGED TOILET |
| | FLOOR PLAN, TOILET ROOMS IN CLASS ROOM |
| | #3, WATER CLOSETS SHALL NOT INTRUDE IN- |
| | TO 5' TURNING RADIUS. ROOM NEEDS TO BE |
| | MINIMUM 7'5". |
| | 4) SHT A7.0 HDCP WATER CLOSETS SHALL BE |
| | 1'6" FROM CENTER OF FIXTURE TO WALL OR |
| | PARTITION. PLEASE SHOW ON DETAIL. |
| | 5) SHT A8.0 KITCHEN SINK DETAIL SHALL |
| | COMPLY WITH 11-4.24 AND ALL SUBSECTIONS. |
| | PLEASE SHOW ON DETAIL. |
| | 6) SHTS P-1, P-2, & P-3 NO SANITARY OR |
| | WATER SHOWN FOR KITCHEN SINK ON FLOOR |
| | PLAN OR ISOMETRICS. PLEASE ADD TO PLANS. |
| | SHT P-3 WATER ISOMETRIC, AIR CHAMBERS |
| | ARE NOT APPROVED. WATER HAMMER ARRESTORS |
| | ARE REQUIRED FOR ALL QUICK CLOSING VALV- |
| | ES, (DISH WASHER, ICE MAKER, WASH MACH- |
| | INES). LOCATE WATER HAMMER ARRESTORS |
| | NEAR FIXTURES IN AN "EFFECTIVE RANGE", |
| | NOT AT TOP OF DROP OVERHEAD AS SHOWN. |
| | 7) PLEASE SHOW DETAILS FOR DRINKING |
| | FOUNTAINS. PLEASE SHOW COMPLIANCE OF |
| | SEC 11-4.15 AND ALL SUBSECTIONS AND SEC |
| | 11-4.1.3(10) FOR THOSE WHO HAVE DIFFICUL |
| | TY BENDING 0R STOOPING. |
| | |
| | REVIEW BY KEN STEVENS |