Plan Review Notes
Plan Review Notes For Permit 02060943
Permit Number 02060943
Review Stop P
Sequence Number 1
Notes
Date Text
2002-07-06 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT D1.0 ALL PLUMBING LINES CAPPED
 FOR DEMO SHALL BE INSPECTED BEFORE COVER
 ING.
 2) SHTS A2.0 & A7.0 ENLARGED TOILET
 FLOOR PLAN, SHOW 5' TURNING RADIUS FOR
 BOYS AND GIRLS TOILET ROOMS.
 3) SHTS A2.0 & A7.0 ENLARGED TOILET
 FLOOR PLAN, TOILET ROOMS IN CLASS ROOM
 #3, WATER CLOSETS SHALL NOT INTRUDE IN-
 TO 5' TURNING RADIUS. ROOM NEEDS TO BE
 MINIMUM 7'5".
 4) SHT A7.0 HDCP WATER CLOSETS SHALL BE
 1'6" FROM CENTER OF FIXTURE TO WALL OR
 PARTITION. PLEASE SHOW ON DETAIL.
 5) SHT A8.0 KITCHEN SINK DETAIL SHALL
 COMPLY WITH 11-4.24 AND ALL SUBSECTIONS.
 PLEASE SHOW ON DETAIL.
 6) SHTS P-1, P-2, & P-3 NO SANITARY OR
 WATER SHOWN FOR KITCHEN SINK ON FLOOR
 PLAN OR ISOMETRICS. PLEASE ADD TO PLANS.
 SHT P-3 WATER ISOMETRIC, AIR CHAMBERS
 ARE NOT APPROVED. WATER HAMMER ARRESTORS
 ARE REQUIRED FOR ALL QUICK CLOSING VALV-
 ES, (DISH WASHER, ICE MAKER, WASH MACH-
 INES). LOCATE WATER HAMMER ARRESTORS
 NEAR FIXTURES IN AN "EFFECTIVE RANGE",
 NOT AT TOP OF DROP OVERHEAD AS SHOWN.
 7) PLEASE SHOW DETAILS FOR DRINKING
 FOUNTAINS. PLEASE SHOW COMPLIANCE OF
 SEC 11-4.15 AND ALL SUBSECTIONS AND SEC
 11-4.1.3(10) FOR THOSE WHO HAVE DIFFICUL
 TY BENDING 0R STOOPING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377