| Plan Review Notes For Permit 02060943 |
| Permit Number |
02060943 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-24 00:00:00 | DENIED: | | | | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | | RETURN AIR SHALL BE EQUAL TO SUPPLY | | | AIR BY MEANS OF AIR TRANSFER OR A RETURN | | | AIR (JUMPER).THE FOLLOWING ROOMS NEED | | | TO COMPLY: | | | CONFERENCE RM 1 | | | CLASS RM 11 | | | OFFICE # 1, 2, 3, 4, 5, 6, 7, 8, & 9 | | | | | | NO COMBUSTIBLES ABOVE THE CEILING IN THE | | | RETURN AIR PLENUM AS PER 2001 FBC(M) | | | 606.2.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|