2002-07-02 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT IT IS NOTED THAT AIC
 RATING IS SHOWN FOR PANELS AND RK FUSES
 FOR ALL DISCS. PLEASE CLARIFY MDP SHOWN
 AAS MAIN BRKR WITH BRKR MAINS? PLEASE
 CORRELATE.
  
 2)NOTE: PLEASE NOTE A SECOND ELECTRICAL
 SERVICE IS NOT PERMITTED PER 230-2
 PLEASE PROVIDE INFORMATION FOR FIRE
 SEPARATION FOR SPACE TO INCLUDE DETAIL
 GOING ALL THE WAY UP TO ROOF STRUCTURE.
 WALL DETAIL ON A6.1 DOES NOT GO ALL THE
 WAY UP TO ROOF DECK?
  
 3)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 AND CLARIFY MEZZANINE??
  
 4)NOTE: PLEASE CLARIFY GROUNDING
 ELECTRODE COMING FROM MDP AND NOT METER-
 CAN?
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  