Plan Review Notes
Plan Review Notes For Permit 02060943
Permit Number 02060943
Review Stop B
Sequence Number 1
Notes
Date Text
2002-07-16 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02060943
 ADD: 7719 S DIXIE HWY
 CONT: CMB CONSTRUCTION GROUP
 TEL: (954) 384-7373
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) VALUATION TO LOW, PROVIDE SIGNED
 CONTRACT WITH COMPLETE PROJECT COST.
 BASED ON DATA COMPILED BY SBCCI USING
 MARSHALL SWIFT PUBLICATION, A TENANT
 FIT UP AT @ 40 % OF TOTAL BUILD OUT:
 $ 541,838.00
  
 2)11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY. SHOW PUBLIC TRANSPORTATION
 DROP OFF, HANDICAPPED PARKING, ACCESS
 TO BUILDING CURB CUTS ETC...
  
 3)11-4.1.3(3) GROUND & FLOOR SURFACES
 ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE
 ROOMS & SPACES SHALL COMPLY WITH
 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE)
 A STATIC COEFFICIENT OF FRICTION OF 0.6
 IS RECOMENDED FOR ACCESSIBLE ROUTES
 AND 0.8 FOR RAMPS.
  
 4) THERE IS (2) COMMENTS ABOUT AN INTER-
 IOR MEZZANINE, BUT NOWHERE IS THE INDICA
 TION AS TO ITS SIZE OR USAGE OR IF IT IS
 TO BE DELETED?VERTICAL ACCESSIBILITY?
  
 5) SHEET A-2.0 INDICATES W-2 " EXISTING
 MEZZANINE TO BE CLOSED UP COMPLETELY
 FROM FIRST FLOOR W/1 HR RATEDPARTI-
 TIONS VERIFY EXTEND AT SITE".PROVIDE
 MORE DETAIL? THE DIMISSING WALL AT THE
 MEZZANINE LEVEL MAY REQUIRE A 2 OR 3 HR
 RATING DEPENDING ON S1 OR S2 STORAGE?
 704.1 TABLE SEE ASSEMBLY OR EDUCATIONAL
 VS STORAGE 2 HRS HORIZONTAL ASSEMBLIES.
  
 6) ISLE BETWEEN DOOR 9/ 14 INDICATES A
 WIDTH OF 5'-10", FL BLD CODE 1021.2.2
 MINIMUM OF 6'-0" ISLE WIDTH.
  
 7) FL BLD CODE 10.21.1 SPECIFY THE AGE
 OF THE STUDENTS TO USE THIS FACILITY?
  
 8) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 9)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 10)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7.
  
 11) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 12)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORT:
 A) STOREFRONT DOORS/ WINDOWS
  
 13)SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.
  
 14)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 15)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 16) AT REAR OF BUILDING, THE EXTERIOR
 STAIRS, PLANS DO NOT INDICATE A SERIES
 OF WINDOWS, RATE AS REQUIRED FOR EXTER-
 IOR STAIRWAY.
  
 17)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026