Plan Review Notes
Plan Review Notes For Permit 02060883
Permit Number 02060883
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-06-18 00:00:001) PLEASE PROVIDE PRODUCT APPROVALS FOR
 3M FIREWRAP OR EQUAL.
  
 2) INSUFFICIENT AIR VELOCITY FROM
 EXHAUST DUCT. EXHAUST DUCT TO PROVIDE
 AT LEAST 1500 CFM THROUGH THE DUCT.
  
 3) THE EXHAUST DUCT IS TO BE A MINIMUM
 OF AT LEAST TEN FEET FROM ADJACENT
 BUILDINGS, PROPERTY LINES, ETC.
  
 4) PLEASE CLARIFY EF-1 LOCATION TO
 PROXIMITY OF SF-1.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497