| Plan Review Notes For Permit 02060883 |
| Permit Number |
02060883 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-18 00:00:00 | 1) PLEASE PROVIDE PRODUCT APPROVALS FOR | | | 3M FIREWRAP OR EQUAL. | | | | | | 2) INSUFFICIENT AIR VELOCITY FROM | | | EXHAUST DUCT. EXHAUST DUCT TO PROVIDE | | | AT LEAST 1500 CFM THROUGH THE DUCT. | | | | | | 3) THE EXHAUST DUCT IS TO BE A MINIMUM | | | OF AT LEAST TEN FEET FROM ADJACENT | | | BUILDINGS, PROPERTY LINES, ETC. | | | | | | 4) PLEASE CLARIFY EF-1 LOCATION TO | | | PROXIMITY OF SF-1. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|