2002-06-26 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT LOAD CALCAULATIONS PER
 220,215-5.
  
 2} INDICATE LOCATION OF SMOKE DETECTORS
 ON PLAN.
  
 3} IN THE AREAS WHERE NEW WIRING IS
 INSTALLED ALSO SHOW EXISTING AND
 INDICATE SAME.
  
 4} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATEDAND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392