2002-07-12 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02060877
 ADD: 338 VALLEY FORGE RD
 CONT: JOHNSON & BARRETT CONST INC
 TEL: 329-7088
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 SHEET A-4 NOT SIHNED/ SEALED
  
 2) SHEET A-2 VARIOUS FOUNDATION DETAILS
 1804.1.3 THE BOTTOM OF THE FOUNDA-
 TION SHALL EXTEND NO LESS THAN 12"
 BELOW FINISH GRADE.NO DIMENSIONS GIVEN?
  
 3) SHEET A-2 DETAIL 8: DETAIL IMPLIES
 THAT THE ADDITIONAL 3X6 TO BE SCABBED
 TO THE EXISTING TRUSS, THERE IS NO INFOR
 MATION AS TO HOW TO RESTRICT THE ADDITIO
 NAL UPLIFT BEING IMPOSED ON THIS CONDI-
 TION
  
 4) SHEET A-2 DETAIL 7: INDICATES AN
 "ANCHOR BOLT" 6" X 5/8"?
  
 5) SHEET A-2 DETAIL 1: THE USE OF PECKY
 CYPRESS 1X6 T&G V JOINT DECKING, HOW
 ARE YOU GOING TO COMPLY WITH ROOFING
 NAILS ARE TO PENETRATE THE DECK 3/4INCH.
 WILL THIS BE A APPEARENCE PROBLEM?
  
 6) SHEET A-2 DETAIL 4 INDICATE WHAT TYPE
 FASTENR SHALL BE USED FOR THE 2" RIGID
 INSULATION + 3/4 "PLYWOOD DECKING?
  
 7) RAFTER SPACING NOT GIVEN FOR LIVING
 ROOM?
  
 8) 2309.1.7 COLLAR TIES OF 1X6 SHALL BE
 INSTALLED IN THE UPPER THIRD OF THE
 ROOF HEIGTH TO EVERY THIRD PAIR OF
 RAFTERS.
  
 9) THIS SET OF PLANS IS INCOMPLETE,
 THERE ARE 2 PAGES OF HAND DRAWN DETILS
 REFRENCING A "S-1" THAT IS NOT INCORP-
 ORATED INTO THIS SET OF PLANS, A
 THOROUGH REVIEW CAN NOT BE ACCOMPLISHED,
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026