| Plan Review Notes For Permit 02060778 |
| Permit Number |
02060778 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-07-16 00:00:00 | 1) DOOR SCHEDULE INDICATES THAT A | | | SOLENOID WILL BE CONNECTED TO THE | | | DOOR LATCH. ONLY DELAYED EGRESS OR | | | ACCESS CONTROLLED EGRESS WILL BE | | | ALLOWED ON REQUIRED EXIT DOORS. PLEASE | | | SEE NFPA 101, 2000 EDITION, CHAPTER 7. | | | | | | 2) EXIT DOOR LOCKS SHALL NOT REQUIRE | | | THE USE OF ANY KEYS, TOOLS, OR | | | SPECIAL KNOWLEDGE TO OPERATE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|