| Plan Review Notes For Permit 02060714 |
| Permit Number |
02060714 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2003-07-03 00:00:00 | DENIED: BUILDING PERMIT 02091035 | | | | | | 1.REVISED PLAN FOR SHEET M-2.1R, | | | INDICATE NO RETURN AIR FROM BEDROOM | | | AREAS.COMMENT #4 HAS BEEN CHANGED TO | | | READ - "RETURN AIR TRANSFER GRILLES | | | OMITTED PER CODE".THIS WAS NOT OMITTED | | | FROM THE CODE AND IS A REQUIREMENT | | | 2001 FBC(M) 601.4. | | | | | | 2.1ST FLOOR PLAN FOR BUILDING C - PLAN | | | INDICATES DUCT FROM AHU 3 PENETRATING | | | A 1HR WALL (SAUNA) WITH NO FIRE DAMPERS. | | | RETURN AIR NOT IDENTIFIED FROM AHU 3. | | | | | | APPROVED - SUMBITTAL FOR THE LEG | | | EXTENSION FOR THE "ALUMA-STAND HD". | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|