Plan Review Notes
Plan Review Notes For Permit 02060714
Permit Number 02060714
Review Stop M
Sequence Number 4
Notes
Date Text
2003-07-03 00:00:00DENIED: BUILDING PERMIT 02091035
  
 1.REVISED PLAN FOR SHEET M-2.1R,
 INDICATE NO RETURN AIR FROM BEDROOM
 AREAS.COMMENT #4 HAS BEEN CHANGED TO
 READ - "RETURN AIR TRANSFER GRILLES
 OMITTED PER CODE".THIS WAS NOT OMITTED
 FROM THE CODE AND IS A REQUIREMENT
 2001 FBC(M) 601.4.
  
 2.1ST FLOOR PLAN FOR BUILDING C - PLAN
 INDICATES DUCT FROM AHU 3 PENETRATING
 A 1HR WALL (SAUNA) WITH NO FIRE DAMPERS.
 RETURN AIR NOT IDENTIFIED FROM AHU 3.
  
 APPROVED - SUMBITTAL FOR THE LEG
 EXTENSION FOR THE "ALUMA-STAND HD".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.