| Plan Review Notes For Permit 02060714 |
| Permit Number |
02060714 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-08-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) SHT A7.4 - REQUIREMENT #7 IS FOR ALL | | | ASPECTS FOR USABLE KITCHENS & BATHROOMS | | | AND NOT JUST MANUVERING AND CLEAR FLOOR | | | SPACE AROUND FIXTURES AS STATED. | | | 2) SHTS A2-4, A3-5, & A4-4 PLEASE SHOW | | | LOCATION OF ALL SECONDARY ROOF DRAINS. | | | 3) SHT A7-4 HDCP STALL DETAIL SHOWS 5'8" | | | TO TOP OF LAV. PER 11-4.19.2 HEIGHT MAX. | | | 2'10" TO TOP OF LAV. | | | 4) FROM PREVIOUS REVIEW: - SHT A-4.2, | | | THE CLEAR FLOOR SPACE FOR THE LAV'S ARE | | | NOT SHOWN. WATER CLOSET SHALL NOT INTR | | | DE INTO CLEAR FLOOR SPACE FOR LAV. | | | 5) FROM PREVIOUS REVIEW: BAR SINK DETAIL | | | NOT SHOWN. PARALLEL APPROACH STILL RE- | | | QUIRES THAT COUNTER SHALL BE 2'10" OFF | | | FLOOR. PLEASE INDICATE HEIGHT PER 11-4. | | | 24.3 | | | 6) SHT P2.9 MASTER BATH, WATER CLOSET | | | SHALL BE 18" OFF WALL AND BIDET IS REQ- | | | UIRED TO BE MINIMUM OF 30" CENTER TO | | | CENTER FROM W/C. SEC 405.3.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|