Plan Review Notes
Plan Review Notes For Permit 02060714
Permit Number 02060714
Review Stop P
Sequence Number 3
Notes
Date Text
2002-08-26 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A7.4 - REQUIREMENT #7 IS FOR ALL
 ASPECTS FOR USABLE KITCHENS & BATHROOMS
 AND NOT JUST MANUVERING AND CLEAR FLOOR
 SPACE AROUND FIXTURES AS STATED.
 2) SHTS A2-4, A3-5, & A4-4 PLEASE SHOW
 LOCATION OF ALL SECONDARY ROOF DRAINS.
 3) SHT A7-4 HDCP STALL DETAIL SHOWS 5'8"
 TO TOP OF LAV. PER 11-4.19.2 HEIGHT MAX.
 2'10" TO TOP OF LAV.
 4) FROM PREVIOUS REVIEW: - SHT A-4.2,
 THE CLEAR FLOOR SPACE FOR THE LAV'S ARE
 NOT SHOWN. WATER CLOSET SHALL NOT INTR
 DE INTO CLEAR FLOOR SPACE FOR LAV.
 5) FROM PREVIOUS REVIEW: BAR SINK DETAIL
 NOT SHOWN. PARALLEL APPROACH STILL RE-
 QUIRES THAT COUNTER SHALL BE 2'10" OFF
 FLOOR. PLEASE INDICATE HEIGHT PER 11-4.
 24.3
 6) SHT P2.9 MASTER BATH, WATER CLOSET
 SHALL BE 18" OFF WALL AND BIDET IS REQ-
 UIRED TO BE MINIMUM OF 30" CENTER TO
 CENTER FROM W/C. SEC 405.3.1
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377