Plan Review Notes
Plan Review Notes For Permit 02060714
Permit Number 02060714
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2002-09-24 00:00:001) SIGNS ARE REQUIRED IN EACH STAIRWELL
 INDICATING THE STAIR NUMBER, THE
 TERMINUS TOP AND BOTTOM OF THE STAIR,
 AND THE STORY, AND THE DIRECTION OF
 EXIT DISCHARGE AND ANY ROOF ACCESS.
  
 2) A SMOKE DETECTOR IS REQUIRED ABOVE
 THE FIRE ALARM CONTROL PANEL.
  
 3) THERE APPEARS TO BE SEVERAL ISSUES
 WITH THE FIRE PUMP CONTROLLER. UNTIL
 ELECTRICAL PLAN REVIEW ISSUES ARE
 RESOLVED WITH THE FIRE PUMP,THIS OFFICE
 CANNOT SIGN OFF ON THE PLANS.
  
 4) ALL THREADS ARE TO BE NST NOT MIAMI
 STANDARDS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910