2002-09-20 00:00:00***************** UNSAT **************
  
 PLANS REVIEWED THIRD TIME.
 PLEASE NOTE THAT COMMENTS ARE STILL NOT
 ADDRESSED FOR FIRE PUMP MAIN, FIRE PUMP
 SPECS AND FIRE PUMP CONTROLLER.
  
 PLEASE NOTE ELECTRICAL ENGINEER WAS
 CALLED ON 9/19/02 WENT OVER ISSUES.
 ENGINEER MENTIONED FIRE PUMP CONTROLLER
 WAS CHANGING AND NEW SUBMITTALS WERE
 COMING IN.
 9/20/02
 PLEASE NOTE AS PER CONVERSATION WITH
 JOSLYN FIRE PUMP CO. FIRE PUMP CONTROLS
 AND ASSC FIRE PUMP EQUIPMENT WAS NOT
 CHANGING AND A NEW RISER DIAGRAM IS
 NEEDED TO ADDRESS SECONDARY OVERCURRENT
 PROTECTION WHICH IS NOT PERMITTED.
 MAIN DISC IS GOING TO BE REVISED DELET-
 -ING OCP.
 PLEASE NOTE DISCONNECTING MEANS FOR
 "JOCKEY PUMP" IS TO BE SERVICE RATED
 AND WILL ALSO BE REVISED ON E5.1.
 PLEASE NOTE, "NOTES' ON E-5.1 ARE TO
 BE REVISED TO CORRELATE WITH FIRE PUMP
 COMPANYS REQ`MENTS AND TO MEET NEC. ARTS
 695-4,695-5, 430-110,430-151. PLEASE
 ALSO SEE NFPA-20 FOR FIRE PUMPS REQ`.
 6-5.1.1.1.
  
  
 PLEASE REVISE RISER DIAGRAM AND RESUB
 WHEN ALL REVIEWS ARE COMPLETE.
 FEES WILL BEOWED FOR PLAN REVIEW DONE.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW