Plan Review Notes
Plan Review Notes For Permit 02060714
Permit Number 02060714
Review Stop B
Sequence Number 3
Notes
Date Text
2002-09-06 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02060714
 ADD: 1600 PRESIDENTIAL WAY
 CONT: AVS CONST CORP
 TEL: (954)961-3848
 ARCH: CLEMENT DIFILLIPPO
 TEL: (305)672-6312
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 ******PLAN REVIEW******
 1) SHEET A-7.1 DOORS, REQUIRED RATINGS
 A) ENTRY DOORS TABLE 705.1.2, EXIT
 ACCESS CORRIDORS- OPENING PROTECTIVES
 SHALL BE 20MIN. & CLOSERS.
  
 2) REFUSE CHUTE ROOMS & REFUSE TERMINA-
 TION ROOMS OPENING PROTECTIVES SHALL BE
 45 MIN WITH CLOSERS. DEMONSTRATE 45 MIN
 WITH LOUVER?
  
 3) 1010.3 EXIT PASSAGEWAYS, EXCEPTION,
 A MAXIMUM OF 50% OF THE REQUIRED NUMBER
 OF EXITS AND 50 % OF THE REQUIRED EXIT
 CAPACITY SHALL BE PERMITTED TO DISCHARGE
 THROUGH AREAS ON THE LEVEL OF EXIT DIS-
 CHARGE PROVIDED ALL THE FOLOWING ARE MET
 SEE 1-4. SEE ATTACHMENTS TO 2 STAIR
 TOWERS AS HOW THIS COULD BE ACCOMPLISHED
 WITH LITTLE ADITIONAL COST.
  
 4) DOOR 57 EXIT DOORS OF THE STAIR TOWER
 NO INDICATION ASTO HOW TO HANDLE LIMIT-
 ING THE PUBLIC ACCESS TO THE ROOF VS
 THE FIRE DEPARTMENT IN TIME OF NEED?
  
 5) DISSCUSSION OF ROOF TRUSSES, AS WELL
 AS SKYBRIDGE.
  
 TYPE IV UNPROTECTED/ SPRINKLERED BLDG.
 TRUSSES TO BE EITHER FIRE RETARDANT
 TREATED WOOD OR METAL FRAMED TRUSSES
 WITH FIRE RETARDANT TREATED PLYWOOD.
  
 TYPE V UNPROTECTED/ SPRINKLERED BLDG.
 MAY USE WOOD FOR TRUSSES AND ROOFING,
 DRAWBACK IS (ASSUMED PROPERTY LINE)
 10'-20' 2HR RATED WALLS WHICH BLOCK WILL
 TAKE CARE OF BUT 1 1/2 HR OPENING PROTEC
 TIVES!!!!! FOR A1-A2, B1-B2, COURTYARD
 OPENINGS!!!!EITHER WILL WORK. THE TYPE
 IV ALLOWED FOR NONCOMBUSTIBLE WINDOW
 AND DOORS ONLY.
  
 6) AS DISCUSSED WITH CAPTAIN CARSILLO
 THESE DRAWINGS DO NOT HAVE FIRE SPRINK-
 LER DRAWINGS NOR STANDPIPE FOR STAIR-
 WELLS. THE ORIGINAL SET DID HAVE THIS
 INFORMATION!
  
 7)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 8) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) WINDOWS
 B) MULLIONS
 C) DOORS ALL SWING ALL TYPES, LOUVERS?
 SLIDING DOORS, DOORS W/ SIDELIGHTS
 D) ROOFING ASSEMBLIES
  
 9)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 11)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
  
 12)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026