| Plan Review Notes For Permit 02060714 |
| Permit Number |
02060714 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-09-03 00:00:00 | DENIED: | | | | | | BUIDLING COMMENTS (JIM WITMERE) ITEM | | | #26 & 27: | | | | | | RESPONSE TO SHAFT ENCLOSURE - SHEET | | | A7-3 DETAIL "L" INDICATES A "SHAFTWALL" | | | WITH A REFERENCE TO UL LISTING U497. | | | THIS LISTING INDICATES A NONBEARING WALL | | | RATING - 2 HR. WHICH IS NOT A "SHAFT" | | | ASSEMBLY.PLEASE PROVIDE UL LISTING | | | FOR A SHAFT ASSEMBLY NOT A WALL (SEE UL | | | DIRECTORY 2002 EDITION, VOLUME 2 PAGE | | | 1075 - FIRE RESISTANCE DUCT ASSEMBLIES). | | | | | | MECHANICAL COMMENTS (NANCY DENMARK) ITEM | | | #6: | | | | | | PLANS HAVE NOT BEEN REVISED TO INDICATE | | | SPRINKLER HEAD OR ACCESS IN THE SHAFT | | | FOR THE DRYER EXHAUST. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|