2002-09-03 00:00:00DENIED:
  
 BUIDLING COMMENTS (JIM WITMERE) ITEM
 #26 & 27:
  
 RESPONSE TO SHAFT ENCLOSURE - SHEET
 A7-3 DETAIL "L" INDICATES A "SHAFTWALL"
 WITH A REFERENCE TO UL LISTING U497.
 THIS LISTING INDICATES A NONBEARING WALL
 RATING - 2 HR. WHICH IS NOT A "SHAFT"
 ASSEMBLY.PLEASE PROVIDE UL LISTING
 FOR A SHAFT ASSEMBLY NOT A WALL (SEE UL
 DIRECTORY 2002 EDITION, VOLUME 2 PAGE
 1075 - FIRE RESISTANCE DUCT ASSEMBLIES).
  
 MECHANICAL COMMENTS (NANCY DENMARK) ITEM
 #6:
  
 PLANS HAVE NOT BEEN REVISED TO INDICATE
 SPRINKLER HEAD OR ACCESS IN THE SHAFT
 FOR THE DRYER EXHAUST.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.