Plan Review Notes
Plan Review Notes For Permit 02060714
Permit Number 02060714
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2002-08-14 00:00:001) PREVIOUS FIRE PLAN REVIEW COMMENTS
 # 1,2,AND 3 ARE TO BE NOTED ON THE
 PLANS.
  
 2) YOUR RESPONSE TO FIRE PLAN REVIEW
 COMMENT # 4 IS NOT ADEQUATE. PLEASE
 ADVISE AND REVISE AS NECESSARY.
  
 3) YOUR RESPONSE TO FIRE PLAN REVIEW
 COMMENT # 5 IS NOT ADEQUATE. PLEASE
 ADVISE AND REVISE.
  
 4) PLEASE PROVIDE PRESCRIPTIVE CODE
 REQUIREMENTS FOR THE HANDRAILS AND
 GAURDRAILS.
  
 5) YOUR RESPONSE TO FIRE PLAN REVIEW
 COMMENT # 12 IS NOT ADEQUATE. THE CODE
 DOES NOT SPECIFY OPEN SHAFTS, BUT
 SHAFTS THAT ARE LARGE ENOUGH FOR PERSONS
 TO FALL INTO. PLEASE REVISE PLANS FOR
 THE REQUIRED SIGNAGE.
  
 6) NO MEP PLAN REVIEW COMMENTS COULD
 BE LOCATED. INFORMATION INDICATED THAT
 CERTAIN RESPONSES TO PLAN REVIEW
 COMMENTS COULD BE LOCATED THERE. PLEASE
 ADVISE.
  
 7) THE 2.65 POUNDS SHOWN ON THE FIRE
 SPRINKLER HYDRAULIC CALCULATIONS FOR
 A SAFETY MARGIN IS NOT ACCEPTABLE.
 PLEASE REVISE CALCULATIONS AS NECESSARY.
  
 8) NO LEGAL PAPERWORK PROVIDED WITH
 REGARDS TO THE SINGLE FIRE PUMP THEORY.
  
 9) PLEASE EXPLAIN 12" CURB AT TOP OF
 STAIR.
  
 10) A SMOKE DETECTOR IS REQUIRED ABOVE
 FIRE ALARM CONTROL PANEL.
  
 11) AN EMERGENCY LIGHT FIXTURE IS
 REQUIRED IN THE FIRE PUMP ROOM.
  
 12) A MEETING IS TO BE SCHEDULED FOR
 THE EXITING OF THE BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910