| 2002-08-28 00:00:00 | *************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT NOT ENOUGH |
| | INFORMATION WAS SUBMITTED FOR FIRE |
| | PUMP. PLEASE PROVIDE INFORMATION FOR |
| | CODE LETTER OF FIRE PUMP. 430-151B |
| | NOTE; 1600A OCP. FOR LOCKED ROTOR. |
| | |
| | 2)NOTE: PLEASE PROVIDE INFORMAITON FOR |
| | MEANS OF DISCONNECT LOCATED IN SAME |
| | EQUIPMENT? PLEASE SEE 695-3-A-1. |
| | |
| | 3)NOTE: PLEASE PROVIDE INFORMATION OF |
| | OCP IN FIRE PUMP CONTROLLER AND SETTING |
| | OF OCP OR IS MAIN (1600A) IN BLDG ONE |
| | BEING USED FOR SETTING OF LOCKED ROTOR? |
| | |
| | 4)NOTE: PLEASE NOTE NOTHING SHOWN ON |
| | PANEL SCHEDULE "DA" ON 6.3? |
| | CIRCUITS ARE SHOWN ON 3.8? |
| | |
| | 5)NOTE: PLEASE CLARIFY LOAD CALCS |
| | SHOWN ON SOME HOUSE PANELS. PLEASE NOTE |
| | LOADS SHOWN AS CONN EXCEED MAINS ON SOME |
| | PANELS. PLEASE VERIFY AND OR SHOW LOAD |
| | CALCS.215-5 |
| | |
| | 6)NOTE: PLEASE CLARIFY LOAD/FEEDER |
| | SCHEDULES SHOWN WITH 0.00 AND BLANK |
| | SPACE SHOWN FOR AMPS? SOME ARE SHOWN |
| | ON "MSB" BUT NOT ON OTHERS? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | OR IF A MEETING CAN BE SET UP TO GO |
| | OVER COMMENTS THAT MAY BE MORE CLEAR |
| | IN PERSON. PLEASE CALL. |
| | |