2002-08-28 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT NOT ENOUGH
 INFORMATION WAS SUBMITTED FOR FIRE
 PUMP. PLEASE PROVIDE INFORMATION FOR
 CODE LETTER OF FIRE PUMP. 430-151B
 NOTE; 1600A OCP. FOR LOCKED ROTOR.
  
 2)NOTE: PLEASE PROVIDE INFORMAITON FOR
 MEANS OF DISCONNECT LOCATED IN SAME
 EQUIPMENT? PLEASE SEE 695-3-A-1.
  
 3)NOTE: PLEASE PROVIDE INFORMATION OF
 OCP IN FIRE PUMP CONTROLLER AND SETTING
 OF OCP OR IS MAIN (1600A) IN BLDG ONE
 BEING USED FOR SETTING OF LOCKED ROTOR?
  
 4)NOTE: PLEASE NOTE NOTHING SHOWN ON
 PANEL SCHEDULE "DA" ON 6.3?
 CIRCUITS ARE SHOWN ON 3.8?
  
 5)NOTE: PLEASE CLARIFY LOAD CALCS
 SHOWN ON SOME HOUSE PANELS. PLEASE NOTE
 LOADS SHOWN AS CONN EXCEED MAINS ON SOME
 PANELS. PLEASE VERIFY AND OR SHOW LOAD
 CALCS.215-5
  
 6)NOTE: PLEASE CLARIFY LOAD/FEEDER
 SCHEDULES SHOWN WITH 0.00 AND BLANK
 SPACE SHOWN FOR AMPS? SOME ARE SHOWN
 ON "MSB" BUT NOT ON OTHERS?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 OR IF A MEETING CAN BE SET UP TO GO
 OVER COMMENTS THAT MAY BE MORE CLEAR
 IN PERSON. PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372