| Plan Review Notes For Permit 02060714 |
| Permit Number |
02060714 |
|
| Review Stop |
B |
| Sequence Number |
13 |
|
| Notes |
| Date |
Text |
| 2003-08-04 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 02060714 | | | ADD: 1600 PRESIDENTIAL WAY | | | CONT: AVS CONSTRUCTION | | | TEL: (561)712-9997 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | ROOF OVERFLOWS: | | | ACTION: DENIED | | | | | | 1)1503.4.2 OVERFLOW DRAINS SHALL BE | | | THE SAME SIZE AS ROOF DRAINS, INSTALLED | | | WITH THE INLET FLOW LINE LOCATED 2" | | | ABOVE THE LOWEST POINT OF THE ROOF LINE. | | | OVERFLOW SCUPPERS SHALL BE A MINIMUM OF | | | 4"IN HEIGTH AND SHALL BE PLACED IN WALLS | | | OR PARARETS WITH THE INLET FLOW LINE | | | NOT LESS THAN 2" ABOVE THE ROOF SURFACE. | | | | | | THE SUBMITTAL INDICATES THE BOTTOM OF | | | THE OVERFLOW APPROXIMATELY 11 INCHES | | | ABOVE THE ROOF DECK!!!! | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|