| Date |
Text |
| 2002-07-06 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | FHA AMEND-98 DESIGN MANUAL |
| | |
| | 1) ROUTE PLANS TO PALM BEACH COUNTY |
| | HEALTH UNIT, DIVISION OF ENVIRONMENTAL |
| | HEALTH, 901 EVERNIA ST. WPB 33401 (561) |
| | 355-3018. FOR REVIEW FOR POOL. |
| | 2) SHTS A2-1, A2-2, A2-3, A3-1, A3-2, |
| | A3-3, A3-4, A5-1, & A5-2. ALL UNITS |
| | SHALL COMPLY WITH FHA DESIGN MANUAL RE- |
| | QUIREMENTS 1 THRU 7. SUBMIT DETAILS. |
| | SPECIFY BATHROOM SPECIFICATION "A" OR |
| | "B". SHOW CLEAR FLOOR SPACE FOR ALL FIX- |
| | TURES IN BATHROOMS AND KITCHENS PER DE- |
| | SIGN MANUAL. |
| | 3) SHTS A2-4, A3-5, & A4-4, PLEASE PRO- |
| | VIDE CALCULATIONS FOR PRIMARY AND SECOND |
| | ARY ROOF DRAINS PER SECTIONS 1106, AND |
| | 1107. ADD 1/2 AREA OF VERTICAL WALLS & |
| | AREA OF ROOF THAT DRAIN ONTO ROOF FROM |
| | ABOVE. PLEASE PROVIDE A STORM RISER DIA- |
| | GRAM. SHOW SQ FOOTAGE AS IT ACCUMULATES |
| | IN DRAIN IN SYSTEM. |
| | 4) SHT A4-1 SHOW CLEAR FLOOR SPACE FOR |
| | FIXTURES IN STALLS IN MENS & WOMENS TOI- |
| | LET ROOMS. DOOR SHALL NOT OPEN INTO THE |
| | CLEAR FLOOR SPACE OF ANY FIXTURE. SEC. |
| | 11-4.17.5 |
| | 5) SHOW DETAIL FOR DRINKING FOUNTAIN. |
| | SHOW COMPLIANCE FOR 11-4.15 & ALL SUB- |
| | SECTIONS AND SEC 11-4.1.3(10) FOR THOSE |
| | WHO HAVE TROUBLE BENDING OR STOOPING. |
| | 6) SHT A-4.2 SHOW CLEAR FLOOR SPACE & 5' |
| | TURNING RADIUS IN TOILET ROOM. 11-4.22.2 |
| | DOOR SHALL NOT OPEN INTO CLEAR FLOOR |
| | SPACE OR UNOBSTRUCTED TURNING RADIUS OF |
| | ANY FIXTURE. |
| | 7) SHT A4-2 BAR SINK TO COMPLY WITH SEC. |
| | 11-4.24 & SUBSECTIONS. SHOW DETAIL |
| | 8) SHT P.0.1 PLEASE SUBMIT MANUF. INFOR. |
| | FOR DOMESTIC WATER BOOSTER PUMPS FOR |
| | PRODUCT APPROVAL. SHOW LISTING FOR TEST- |
| | ING AGENCY. |
| | 9) THE DISCHARGE PIPE FROM THE RELIEF |
| | VALVE (T/P) SHALL NOT HAVE ANY TRAPPED |
| | SECTIONS AND SHALL HAVE A VISIBLE AIR |
| | GAP OR AIR GAP FITTING LOCATED IN THE |
| | SAME ROOM AS THE WATER HEATER. SHT P.0.1 |
| | WATER HEATER DETAIL. SECTION 504.7.1 |
| | 607.3 A MEANS OF CONTROLLING INCREASED |
| | PRESSURE CAUSED BY THERMAL EXPANSION |
| | SHALL BE PROVIDED IN ACCORDANCE WITH |
| | SECTIONS 607.3.1 & 607.3.2 |
| | 10) SHT P-0.1 GENERAL NOTES #18, 2-1/2" |
| | AND SMALLER PIPE SHALL BE RUN AT 1/4" |
| | PER FOOT PER TABLE 704.1. GENERAL NOTES |
| | #20 DIELECTRIC UNIONS APPROVED FOR GAS |
| | PIPING ONLY. |
| | 11) SHT P-1.1 PER SECTION 424, 64E-9.004 |
| | (2)(F), SEPARATE SANITARY FACILITIES |
| | SHALL BE PROVIDED & LABLED FOR EACH SEX |
| | & MUST BE LOCATED WITHIN A 200' RADIUS |
| | OF THE NEAREST WATER'S EDGE OF THE POOL. |
| | NUMBER OF FIXTURES PER POOL SIZE. |
| | 12) SEPARATE POOL PERMIT REQUIRED. |
| | 13) SHT P-2.3 APT "A" LOWER LEFT - 2 |
| | SANITARY LINES PICKING UP RISER S-2. |
| | PLEASE CLAIRFY. |
| | 14) SHTS P.2.3 & P.2.4 RELIEF VENT RE- |
| | QUIRED WHERE CONDENSATE EXITS THE BLDG. |
| | PLEASE SHOW ON PLANS. |
| | 15) SHTS P.2.3 & P.2.4 TWO WAY CLEAN OUT |
| | REQUIRED NEAR JUNCTION OF BLDG DRAIN AND |
| | BLDG SEWER. SEC 708.3.5 |
| | 16) SHTS P.2.7 & P.2.8, SHOW DETAILS FOR |
| | HDCP FIXTURES PER 11-4.26 W/C'S, 11-4.18 |
| | URNALS, 11-4.19 LAVS. |
| | 17) A SERVICE SINK IS REQUIRED PER TABLE |
| | 403.1 |
| | 18) SHT P.3.2 SANITARY RISER DIAGRAM, |
| | RISER #3 TUB MISSING FOR BATH #2. |
| | 19) SHT P.3.2 SANITARY RISER DIAGRAM, |
| | FOR BLDGS A & B PLEASE SHOW FIXTURE UNIT |
| | COUNT AS THEY ACCUMULATE IN THE DRAINAGE |
| | SYSTEM. ADD AT EACH BRANCH AT BLDG DRAIN |
| | 20) SHT P.3.3 WATER ISOMETRICS, AIR CHAM |
| | BERS NOT APPROVED. WATER HAMMER ARRESTOR |
| | REQUIRED AT QUICK CLOSING VALVES LOCATED |
| | NEXT TO FIXTURES. 604.9 PLEASE REMOVE |
| | ALL AIRCHAMBERS. |
| | 21) WILL PRESSURE REDUCERS BE REQUIRED |
| | AT UNITS NEAR THE WATER BOOSTER PUMPS? |
| | PLEASE SUBMIT CALCULATIONS FOR DOMESTIC |
| | WATER SYSTEM, SHOWING PRESSURE AT PUMPS |
| | AND AT FURTHEST UNIT FROM PUMPS. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |