| 2002-07-11 00:00:00 | DENIED: | | | | | | 1. PROVIDE OUTSIDE AIR CALCULATIONS FOR | | | ALL SPACES SHOWING COMPLIANCE WITH | | | FBC(M) TABLE 403.3. | | | | | | 2. FBC(M) 601.4 REQUIRES BALANCED AIR | | | RETURN NOT TO EXCEED 0.001 INCH WC. | | | PROVIDE RETURN AIR PATH FOR COMPLIANCE | | | WITH THIS SECTION. | | | | | | 3. EQUIPMENT ON ROOF MOUNTED STANDS, | | | HEIGHT OF STANDS DEPENDS ON WIDTH OF | | | EQUIPMENT. SEE FBC TABLE 1511.7 FOR | | | MINIMUM CLEARANCE. | | | | | | 4. OVERFLOW PROTECTION REQUIRED ON ALL | | | AHU EQUIPMENT. | | | | | | 5.PROVIDE INFORMATION ON FAN SHUT DOWN | | | BY DUCT SMOKE DETECTORS FOR THE UNITS | | | WITH GREATER THAN 2000CFM. | | | | | | 6. DRYER EXHAUST SHAFTS WILL NEED ACCESS | | | FOR THE SPRINKLER HEADS. |
|