Plan Review Notes
Plan Review Notes For Permit 02060714
Permit Number 02060714
Review Stop M
Sequence Number 1
Notes
Date Text
2002-07-11 00:00:00DENIED:
  
 1. PROVIDE OUTSIDE AIR CALCULATIONS FOR
 ALL SPACES SHOWING COMPLIANCE WITH
 FBC(M) TABLE 403.3.
  
 2. FBC(M) 601.4 REQUIRES BALANCED AIR
 RETURN NOT TO EXCEED 0.001 INCH WC.
 PROVIDE RETURN AIR PATH FOR COMPLIANCE
 WITH THIS SECTION.
  
 3. EQUIPMENT ON ROOF MOUNTED STANDS,
 HEIGHT OF STANDS DEPENDS ON WIDTH OF
 EQUIPMENT. SEE FBC TABLE 1511.7 FOR
 MINIMUM CLEARANCE.
  
 4. OVERFLOW PROTECTION REQUIRED ON ALL
 AHU EQUIPMENT.
  
 5.PROVIDE INFORMATION ON FAN SHUT DOWN
 BY DUCT SMOKE DETECTORS FOR THE UNITS
 WITH GREATER THAN 2000CFM.
  
 6. DRYER EXHAUST SHAFTS WILL NEED ACCESS
 FOR THE SPRINKLER HEADS.