Plan Review Notes
Plan Review Notes For Permit 02060714
Permit Number 02060714
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-07-18 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) SUITABLE ROADS ARE TO BE PROVIDED
 FOR FIRE AND PARAMEDICAL EQUIPMENT
 DURING CONSTRUCTION.
  
 3) TEMPORARY STANDPIPE SYSTEMS ARE
 REQUIRED FOR THE BUILDINGS WHEN THEY
 REACH THREE FLOORS OR THIRTY FEET IN
 HEIGHT.
  
 4) SECURITY GATES REQUIRE SEPARATE PLANS
 AND PERMITS. GATES MUST PROVIDE AT
 LEAST TWENTY FEET IN CLEAR WIDTH. WHAT
 PROVISIONS ARE BEING MADE FOR FIRE AND
 PARAMEDICAL INGRESS AND EGRESS. IF
 ELECTRIC, WHAT PROVISIONS WILL BE
 MADE FOR WHEN POWER IS LOST.
  
 5) PLEASE EXPLAIN TRASH/FIRE GATE.
  
 6) PLEASE EXPLAIN EXITING RATIONALE FOR
 COMPLEX.
  
 7) BUILDING ADDRESSES REQUIRED ON
 BUILDING.
  
 8) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 9) TRASH CHUTE MUST EXTEND A MINIMUM OF
 THREE FEET ABOVE THE ROOF.
  
 10) PLEASE INDICATE PRESCRIPTIVE CODE
 REQUIREMENTS FOR ALL HANDRAILS.
  
 11) REQUIRED ELECTRIC POWERED SMOKE
 DETECTORS APPEAR TO BE MISSING FROM
 SOME OF THE UNITS.
  
 12) ALL VERTICAL SHAFTS LARGE ENOUGH
 FOR PERSONS TO FALL INTO SHALL BE
 MARKED "SHAFTWAY" IN RED LETTERS ON A
 WHITE SIGN.
  
 13) SINCE IT APPEARS THAT ONLY ONE
 FIRE PUMP IS PLANNED, LEGAL DOCUEMNTS
 ARE TO BE SUBMITTED THAT THE BUILDINGS
 CANNOT BE SOLD OFF INDIVIDUALLY
 LEAVING ONE BUILDING WITHOUT ONE. THIS
 INFORMATION MUST BE RECORDED.
  
 14) SPRINKLER HEADS APPEAR TO BE
 MISSING FROM THE PLANS.
  
 15) PLEASE PROVIDE OCCUPANT LOADS FOR
 THE BUILDING.
  
 16) PLEASE PROVIDE OCCUPANT LOADS FOR
 THE STAIRS.
  
 17) WHERE ARE THE PORTABLE FIRE
 EXTINGUISHERS LOCATED.
  
 18) KNOX-BOXES WILL BE REQUIRED.
  
 19) PLEASE REVIEW DOOR SCHEDULE. THE
 ONLY RATED DOORS SHOWN ARE THE APARTMENT
 DOORS. OTHER DOORS WILL BE REQUIRED TO
 BE FIRE RATED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910