Plan Review Notes
Plan Review Notes For Permit 02060714
Permit Number 02060714
Review Stop E
Sequence Number 1
Notes
Date Text
2002-07-17 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE LET SPACING ALONG
 KITCHEN COUNTERSPACE NEED TO MEET
 210-52-C-1.
  
 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
 INCLUDES KITCHEN ISLANDS.
  
 3)NOTE" PLEASE NOTE E2.1 PLAN NOTES #5,6
 NEED TO CORRELATE WITH PLANS.
  
 4) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 5) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSING FEW.
 6)NOTE: PLEASE NOTE OUTLETS FOR KITCHEN
 PENINSULARS 210-52-C-3
  
 6)NOTE: PLEASE NOTE MISSING HALLWAY
 RECEPTS PER 210-52H
  
 7)NOTE: PLEASE NOTE BATH RECEPTS TO BE
 SHOWN AS GFI/GFI PROTECTED.210-8
  
 8)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE,
 210-12
  
 9)NOTE: PLEASE NOTE THAT ALL CIRCUITING
 NEEDS TO BE SHOWN ON PLANS INCLUDING
 HOUSE CIRCUITS.
  
 10)NOTE: PLEASE SEE 695-3-A-1.
 IT APPEARS FROM ROOM LAYOUT E4.1 THAT
 THIS IS LOCATED IN THE SAME CABINET??
 PLEASE PROVIDE INFORMATION FOR FIRE PUMP
 CONTROLLER/CABINET.
 PLEASE ALSO NOTE/CLARIFY "JOCKEY PUMP"
 OCP/CONTROL?? SEE 695-6-F.
 PLEASE PROVIDE INFORMATION FOR SIZING
 OF ALL CONDUCTORS AND CONDUITS.
  
 11)NOTE: PLEASE SOME PAGES REFERENCE
 NOTES AND NOTES ARE NOT LISTED?E5.3
  
 12)NOTE: PLEASE SEE LOAD SHOWN FOR PANEL
 "C" IS SHOWN AT 227A`S ON A 225A PANEL?
 PANEL SCHEDULE MENTIONS ON 3RD FLR AND
 RISER SHOWS ON 5TH FLOOR?? PLEASE
 CORRELATE.
  
 13) NOTE: PLEASE CLARIFY, LOAD SHOWN FOR
 RANGE/OVENS ON E6.1 SHOWN AT 12KW AND
 7.8KW ON 6.2 ?? PLEASE CORRELATE.
  
 14)NOTE: PLEASE NOTE THAT LOADS ON PANEL
 -S FOR AHU`S/SPACE HEATING DO NOT
 CORRELATE WITH LOAD CALCULATIONS FOR
 PANELS AND THEN SHOWN EVEN LOWER ON
 LOAD CALCS "MDB`S","MDA`S" IT APPEARS
 THAT IF LOAD CALCUALTIONS CORRELATE,
 SOME LOADS MAY EXCEED 800A RATINGS????
 PLEASE CORRELATE RE-FIGURE LOADS.
  
 15)NOTE: PLEASE NOTE THAT NO GROUNDING
 ELECTRODE SYSTEM WAS SHOWN/SUBMITTED.?
 250-50
 PLEASE SHOW DETAIL FOR ALL MDA`S AND B`S
 COLD WATER, FOOTER STEEL.
  
 PLEASE PROVIDE THE ABOVE INFORMATIN FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372