| 2002-07-17 00:00:00 | **************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE NOTE LET SPACING ALONG |
| | KITCHEN COUNTERSPACE NEED TO MEET |
| | 210-52-C-1. |
| | |
| | 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210-8-A-6. |
| | INCLUDES KITCHEN ISLANDS. |
| | |
| | 3)NOTE" PLEASE NOTE E2.1 PLAN NOTES #5,6 |
| | NEED TO CORRELATE WITH PLANS. |
| | |
| | 4) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | IN THE VICINITY OF BEDROOMS AND CLOSE |
| | PROXIMITY OF STIRWAYS. 2-5.2.1.3 |
| | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| | |
| | 5) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | MISSING FEW. |
| | 6)NOTE: PLEASE NOTE OUTLETS FOR KITCHEN |
| | PENINSULARS 210-52-C-3 |
| | |
| | 6)NOTE: PLEASE NOTE MISSING HALLWAY |
| | RECEPTS PER 210-52H |
| | |
| | 7)NOTE: PLEASE NOTE BATH RECEPTS TO BE |
| | SHOWN AS GFI/GFI PROTECTED.210-8 |
| | |
| | 8)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | PROTECTED CIRCUITS ON PANEL SCHEDULE, |
| | 210-12 |
| | |
| | 9)NOTE: PLEASE NOTE THAT ALL CIRCUITING |
| | NEEDS TO BE SHOWN ON PLANS INCLUDING |
| | HOUSE CIRCUITS. |
| | |
| | 10)NOTE: PLEASE SEE 695-3-A-1. |
| | IT APPEARS FROM ROOM LAYOUT E4.1 THAT |
| | THIS IS LOCATED IN THE SAME CABINET?? |
| | PLEASE PROVIDE INFORMATION FOR FIRE PUMP |
| | CONTROLLER/CABINET. |
| | PLEASE ALSO NOTE/CLARIFY "JOCKEY PUMP" |
| | OCP/CONTROL?? SEE 695-6-F. |
| | PLEASE PROVIDE INFORMATION FOR SIZING |
| | OF ALL CONDUCTORS AND CONDUITS. |
| | |
| | 11)NOTE: PLEASE SOME PAGES REFERENCE |
| | NOTES AND NOTES ARE NOT LISTED?E5.3 |
| | |
| | 12)NOTE: PLEASE SEE LOAD SHOWN FOR PANEL |
| | "C" IS SHOWN AT 227A`S ON A 225A PANEL? |
| | PANEL SCHEDULE MENTIONS ON 3RD FLR AND |
| | RISER SHOWS ON 5TH FLOOR?? PLEASE |
| | CORRELATE. |
| | |
| | 13) NOTE: PLEASE CLARIFY, LOAD SHOWN FOR |
| | RANGE/OVENS ON E6.1 SHOWN AT 12KW AND |
| | 7.8KW ON 6.2 ?? PLEASE CORRELATE. |
| | |
| | 14)NOTE: PLEASE NOTE THAT LOADS ON PANEL |
| | -S FOR AHU`S/SPACE HEATING DO NOT |
| | CORRELATE WITH LOAD CALCULATIONS FOR |
| | PANELS AND THEN SHOWN EVEN LOWER ON |
| | LOAD CALCS "MDB`S","MDA`S" IT APPEARS |
| | THAT IF LOAD CALCUALTIONS CORRELATE, |
| | SOME LOADS MAY EXCEED 800A RATINGS???? |
| | PLEASE CORRELATE RE-FIGURE LOADS. |
| | |
| | 15)NOTE: PLEASE NOTE THAT NO GROUNDING |
| | ELECTRODE SYSTEM WAS SHOWN/SUBMITTED.? |
| | 250-50 |
| | PLEASE SHOW DETAIL FOR ALL MDA`S AND B`S |
| | COLD WATER, FOOTER STEEL. |
| | |
| | PLEASE PROVIDE THE ABOVE INFORMATIN FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |