Plan Review Notes
Plan Review Notes For Permit 02060714
Permit Number 02060714
Review Stop B
Sequence Number 1
Notes
Date Text
2002-07-21 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02060714
 ADD: 1600 PRESIDENTIAL WAY
 CONT: AVSCONST CORP.
 TEL: (954) 961-3848
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 PARK PLACE AT 1600 PRESIDENTIAL WAY
  
 ARCH: CLEMENT DIFILLIPPO
 TELL: (305) 672-6312
 *****GENERAL COMMENTS*****
 1)FL BLD CODE CHAP 5 HEIGTH & AREA OF
 BUIULDINGS NOT DISCLOSED.
  
 2) TYPE OF CONSTRUCTION (603-608) NOT
 DISCLOSED.TABLE 500 REQUIRES A-2 TO BE
 LOCATED ON THE 3RD FLOOR TO BE TYPE II.
  
 3) PLAN REVIEW IS $250.00 / BUILDING
 AMOUNT OF BUILDINGS TO BE DETERMINED!
 THREE VS FIVE!
  
 4) AWNINGS BY SEPERATE PERMIT WITH ASS-
 OCIATED PLANS, FEES & PERMITS.
  
 5) MISSING PAGES, A2-2 NOTES INDICATES
 PAGES A2-6,A2-8 MISSING?
  
 6) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 S5-1 ARDAMAN & ASSOCIATES FILE #
 02-2012.
  
 7)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 8)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 9) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) ALL GLAZED OPENINGS, SLIDING GLASS
 DOORS, WINDOWS & SKYLIGHTS.
 B) EXTERIOR DOORS,UNIT ENTRY DOORS INC.
 C) ROOFING ASSEMBLIES
 D) STORM SHUTTERS FIRST FLOOR WHEN
 APPROVED BY BLDG OFFICIAL SEE
 ATTACHMENT.
  
 10)SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.
  
 11)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 12)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 FIRST FLOOR, WHEN APPOVED BY BLDG
 OFFICIAL, SEE ATTACHMENT.
  
 13) 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 14) 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 15)905.2.1 APPROVED SINGLE-STATION OR
 MULTIPLE STATION SMOKE DETECTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH NFPA 72,
 CHAPTER 2, WITHIN EVERY DWELLING UNIT
 WITHIN AN APARTMENT HOUSE, CONDOMINIMUM,
 OR TOWNHOUSE AND EVERY GUEST OR SLEEPING
 ROOM IN A MOTEL, HOTEL, OR DORMITORY &
 SLEEPING ROOMS IN RESIDENTIAL CARE/
 ASSISTED LIVING OCCUPANCIES. WHERE MORE
 THAN ONE DETECTOR IS REQUIRED TO BE
 INSTALLED WITHIN INDIVIDUAL DWELLING
 UNIT, THE DETECTOR SHALL BE WIRED IN
 SUCH A MANNER THAT THE ACTUATION OF ONE
 ALARM WILL ACTIVATE ALL THE ALARMS IN
 THE INDIVIDUAL UNIT.
  
 16)905.2.1 RESIENTIAL SMOKE ALARMS:
 NFPA 72.A-8-1.2.1(B) ALL SMOKE DETECTORS
 SPECIFIED IN A-8-1.2.1(A) FOR EXISTING
 CONSTRUCTION ARE REQUIRED, AND, IN ADD-
 TION, A SMOKE DETECTOR IS REQUIRED IN
 EACH SLEEPING ROOM.
  
 17)903.8.2 FLOR ST STATUTE 553.895(2)
 ALL RESIDENTIAL BUILD. 3 OR MORE STORIES
 TALL WHETHER DESIGNATED AS TOWNHOUSE,
 CONDOMINIUMS, "APARTMENT HOUSES,
 TENEMENTS, GARDEN APARTMENTS OR BY ANY
 OTHER NAME SHALL BE SUPPLIED BY FIRE
 SPRINKLERS MEETING NFPA 101. NO PLANS
 WERE SUPPLIED.
  
 18) MEANS OF EGRESS: A CONTINUOUS AND
 UNOBSTRUCTED WAY OF TRAVEL FROM ANY
 POINT IN A BUILDING OR STRUCTURE TO A
 PUBLIC WAY, CONSISTING OF THREE SEPERATE
 AND DISTINCT PARTS: (1) THE WAY OF THE
 EXIT ACCESS, (2) THE EXIT, AND (3) THE
 THE WAY OF OF THE EXIT DISCHARGE.
 A MEANS OF EGRESS COMPRISES THE VERTICAL
 AND HORIZONTAL WAYS OF TRAVEL AND
 INCLUDE THE INTERVENING ROOM SPACE,DOORS
 CORRIDORS,PASSAGEWAYS,BALCONIES, STAIRS,
 RAMPS, ENCLOSURES, LOBBIES, HORIZONTAL
 EXITS, COURTS AND YARDS.
  
 19) THIS COMMENT APPLIES FOR BLDG A & B
 1006.2.2.THIS SHALL BE AN ISSUE IF THE
 PLAN REVIEW REVEALS THERE ARE (2) "A"
 BUILDINGS AND (2) "B" BUILDINGS.
 OPEN PORCHES BALCONIES & STAIRWAYS SHALL
 BE LOCATED AT LEAST 10 FT FROM ALL
 ADJACENT PROPERTY LINES AND FROM OTHER
 BUILDINGS ON THE SAME LOT, UNLESS
 OPENINGS IN SUCH BUILDINGS ARE PROTECTED
 BY 3/4 HR FIRE RESISTANT DOORS & WINDOWS
 IF A FIRE WERE TO BREAK OUT ON
 THE LANDING IN FRONT OF THE DOOR OF
 BLDG A1 OR B1 HOW WOULD THE RESIDENT GET
 OUT? THE INTENT OF THE CODE IS TO HAVE
 2 MEANS OF EGRESS?
  
 20)11.4.3.11AREAS OF RESCUE ASSISTANCE
 INDICATE LOCATION AND CONSTRUCTION TYPE
 FOR AREAS OF REFUGE, INDICATE ON PLAN
 WHICH CASE USED (1-7).
  
 21)11-4.3.11.2 STAIRWAY WIDTH, EACH
 STAIRWAY ADJACENT TO AN AREA OF RESCUE
 SHALL HAVE A MINIMUM CLEAR WIDTH OF
 48" BETWEEN HANDRAILS.
  
 22) MISSING RATINGS ON DOORS AS PER
 TABLE 705.1.2. OPENING PROTECTIVES.
  
 23)705.2.4.2 REFUSE AND LAUNDRY CHUTE
 ENCLOSURES. A SHAFT CONTAINING A REFUSE
 OR LAUNDRY CHUTE SHALL BE USED FOR NO
 OTHER PURPOSE ANS SHALL PURPOSE AND BE
 PROTECTED BY A SHAFT ENCLOSURE IN ACCORD
 ANCE WITH 705.2.3. ALL OPENING S INTO
 THE SHAFT ENCLOSURE, ENCLUDING THOSE
 FROM ACCESS ROOMS AND TERMINATION ROOMS,
 SHALL BE PROTECTED IN ACCORDANCE WITH
 TABLE 705.1.2.
  
 24)705.2.4.3. REFUSE & LAUNDRY CHUTE
 ACCESS ROOMS. ACCESS OPENINGS FOR REFUSE
 AND LAUNDRY CHUTES SHALL BE LOCATED IN
 ROOMS OR COMPARMENTS COMPLETELY ENCLOSED
 BY CONSTRUCTION & OPENING PROTECTIVES IN
 ACCORDANCE WITH TABLE 705.1.2.ACCESS
 OPENINGS TO REFUSE AND LAUNDRY CHUTES
 SHALL NOT BE LOCATED IN EXIT ACCESS
 CORRIDORS OR EXIT ENCLOSURES.
  
 25)705.4.6 AUTOMATIC SPRINKLERS. AN
 APPROVED AUTOMATIC SPRINKLER SYSTEM
 SHALL BE INSTALLED AT THE TOP AND AT
 ALTERNATE FLOOR LEVELS IN REFUSE &
 LAUNDRY CHUTES AND IN THE TERMINATION
 ROOMS.
  
 26) SHEET A7-2 DOESN'T INDICATE THE
 RATING ON THE SHAFT WALL OR COMPOSITION
 OF THE WALL, PLEASE PROVIDE A UL LISTING
  
 27) TABLE 705.1.2 SHAFT ENCLOSURES 4
 STORIES AND MORE 2 HR RATING, PLEASE PRO
 VIDE U L RATING FOR BATHROOM EXHAUST,
 DRYER EXHAUST& SHAFTS FOR REFRIGARANT
 PIPING.
  
 28) ELEVATED WALKWAYS, 1604.8:SKYWALK
 SUPPORTS FOR WALKWAYS, WHERE WALKWAYS
 ARE TO BE INSTALLED ABOVE CEILINGS,
 SUPPORTS SHALL BE DESIGNED TO CARRY A
 LOAD OF 200 LBS OCUPYING A SPACE 2 1/2
 SQ FT SO PLACED AS TO PRODUCE MAXIMUM
 STRESS IN THE AFFECTED MEMBERS.
  
 29)3003.6.1 VENTS. HOISTWAYS OF ELEVA-
 TORS SERVING MORE THAN 3 FLOORS SHALL BE
 PROVIDED WITH MEANS OF VENTING SMOKE
 AND HOT GASES TO THE OUTER AIR IN CASE
 OF FIRE.
  
 30)3003.6.2 VENTS SHALL BE LOCATED
 BELOW THE FLOOR OR FLOORS AT THE TOP OF
 THE HOISTWAY, AND SHALL BE EITHER DIR-
 ECTLY TO THE OUTER AIR OR THROUGH NON-
 COMBUSTIBLE DUCTS TO THE OUTER AIR.
  
 31)3003.6.3 THE AREA OF THE VENTS
 SHALL BE NOT LESS THAN 3 SQ FT FOR EACH
 ELEVATOR CAR, WHICHEVER IS GREATER.
  
 32) SHEET M4-1 POWER ROOF EXHAUST FAN
 DETAIL INDICATES THAT IT IS ATTACHED TO
 3/4 " PLYWOOD DECKING VS CONCRETE
 HOLLOW CORE PLANKING?
  
 33)1511.7 ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7.
  
 34)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 35)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 36) 1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 37) 1204.3 SHOWERS. SHOWER COMPARTMENTS
 SHALL HAVE FLOORS AND WALLS CONSTRUCTED
 OF SMOOTH, CORROSION RESISTANT AND NON-
 ABSORBENT WATER-RESISTANT MATERIALS TO A
 HEIGHT OF NOT LESS THAN 70" ABOVE THE
 COMPARTMENT FLOOR AT DRAIN.
  
 38) SHEET S1-1 NOTE:TYPICAL 5" CONC.
 FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 39)1814.2.4 WALL & FLOOR JOINTS AND
 PENETRATIONS SHALL BE MADE WATER TIGHT
 USING APPROVED METHODS & MATERIALS.
  
 40) SHEET S5-5 DOESN'T INDICATE THE HR
 RATING FOR TYPE II BUILD. PROVIDE ADDI-
 TIONAL INFORMATION. MEETING ROOM 3RD
 FLOOR.
  
 41) SHEET S5-4 DOESN'T INDICATE THE MAG-
 NITUDE OF LOADS, VERTICAL, HORIZONTAL &
 LATERAL THAT SHALL BE RESISTED BY THE
 TRUSSES. NO INFORMATION ON TRUSS ANCHOR
 MANUFACTURER OR MODEL?
  
 42) NO INFORMATION ON THE STAIRWELL
 RAILINGS?
  
 43)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026