| Plan Review Notes For Permit 02060667 |
| Permit Number |
02060667 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-02-12 00:00:00 | ************* UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE PREVIOUS NOTES, | | | PLEASE SIZE SERVICE ENTRANCE CONDUCTORS | | | PER 310-15. MAINS ADD UP TO 385A SERVICE | | | ON RESIDENTIAL, OR HAVE A MAIN THAT | | | LIMITS SIZE OF SERVICE TO SERVICE ENTRAN | | | -CE CONDUCTORS. | | | PLEASE ALSO SEE SIZING OF NEUTRAL,SHOWN | | | AS #3, PLEASE PROVIDE NEUTRAL LOAD | | | CALCULATIONS. | | | | | | 2)NOTE : PLEASE SEE 210-52-C1 FOR | | | OUTLET SPACING SERVING KITCHEN COUNTER- | | | -SPACE. | | | | | | 3)NOTE: MISSING A COUPLE OF RECEPTS PER | | | 210-52 | | | | | | 4)NOTE: PLEASE SEE 250-66 FOR SIZING OF | | | GROUNDING ELECTRODE CONDUCTOR. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|