2003-02-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02060667
 ADD: 509 FLAMINGO DR
 CONT: WELLINGTON REMODELING INC
 TEL: (561)798-3330
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) COMMENT (9) FROM PREVIOUS REVIEW:
 STORM SHUTTERS ARE TO BE PROVIDED BY
 OWNER. ARRE THEY TO BE PROVIDED UNDER
 THIS PERMIT, NO INFORMATION HAS BEEN
 SUBMITTED. THE PRODUCT TESTING REPORT
 WILL HAVE TO INDICATE A STAND OFF OF THE
 MINIMUM DEFLECTION DISTANCE SINCE NO
 WINDOW BUCK DETAIL IS GIVEN.
 A KEY PLAN FOR SHUTTER INSTALATION
 & A COMPLETE ANCHOR SCHEDULE SHALL BE RE
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 2) COMMENTS 9-13 DEALING WITH PRODUCT
 TESTING REPORTS, NO REPORTS WERE SUBMIT-
 TED FOR THE FOLLOWING:
 A) WINDOWS
 B) EXTERIOR DOORS SINGLE, AND FRENCH
 C) MULLIONS
 D) ROOFING ASSEMBLIES
 E) SWING GARAGE DOORS
 F) STORM SHUTTERS
 EVEN IF THE OWNER ELECTS TO SHUTTER THE
 GLAZED OPENINGS, CODE STILL REQUIRES
 TESTING FOR WIND! THE PRODUCT TESTING RE
 PORTS REFLECT THIS.WE ACCEPT SBCCI OR
 DADE COUNTY . REPORTS OTHER THAN THESE
 HAVE TO BE SITE SPECIFIC & ON W.P.B.
 FORMS MEETING SITE SPECIFIC REQUIREMENTS
  
 1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS. IF THE DESIGNER ISN'T
 GOING TO HAVE WINDOW BUCKS, PRODUCT TEST
 ING REPORTS FOR WINDOWS WILL HAVE TO
 INDICATE A FLANGED FASTENING SYSTEM. THE
 OTHER ISSUE WILL BE THE MINIMUM DISTANCE
 STORM SHUTTERS WILL HAVE TO STAND OFF
 FOR DEFLECTION, USALLY 2 1/2" TO 3".
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026