| 2003-02-19 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 02060667 |
| | ADD: 509 FLAMINGO DR |
| | CONT: WELLINGTON REMODELING INC |
| | TEL: (561)798-3330 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) COMMENT (9) FROM PREVIOUS REVIEW: |
| | STORM SHUTTERS ARE TO BE PROVIDED BY |
| | OWNER. ARRE THEY TO BE PROVIDED UNDER |
| | THIS PERMIT, NO INFORMATION HAS BEEN |
| | SUBMITTED. THE PRODUCT TESTING REPORT |
| | WILL HAVE TO INDICATE A STAND OFF OF THE |
| | MINIMUM DEFLECTION DISTANCE SINCE NO |
| | WINDOW BUCK DETAIL IS GIVEN. |
| | A KEY PLAN FOR SHUTTER INSTALATION |
| | & A COMPLETE ANCHOR SCHEDULE SHALL BE RE |
| | FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | 2) COMMENTS 9-13 DEALING WITH PRODUCT |
| | TESTING REPORTS, NO REPORTS WERE SUBMIT- |
| | TED FOR THE FOLLOWING: |
| | A) WINDOWS |
| | B) EXTERIOR DOORS SINGLE, AND FRENCH |
| | C) MULLIONS |
| | D) ROOFING ASSEMBLIES |
| | E) SWING GARAGE DOORS |
| | F) STORM SHUTTERS |
| | EVEN IF THE OWNER ELECTS TO SHUTTER THE |
| | GLAZED OPENINGS, CODE STILL REQUIRES |
| | TESTING FOR WIND! THE PRODUCT TESTING RE |
| | PORTS REFLECT THIS.WE ACCEPT SBCCI OR |
| | DADE COUNTY . REPORTS OTHER THAN THESE |
| | HAVE TO BE SITE SPECIFIC & ON W.P.B. |
| | FORMS MEETING SITE SPECIFIC REQUIREMENTS |
| | |
| | 1707.4.3 EACH EXTERIOR DOOR |
| | ASSEMBLY NOT COVERED BY 1707.4.2 |
| | (GLAZED DOORS) SHALL BE LISTED AND TEST- |
| | ED FOR A PERIOD EQUAL TO THE QUANITY |
| | 3600/ V WHERE THE TIME PERIOD IS IN |
| | SECTIONS AND V IS IN MILES PER HR TAKEN |
| | FROM FIGURE 1606. THE TIME PERIOD SHALL |
| | ALSO INCLUDE A 10 SECOND PERIOD AT A |
| | LOAD EQUAL TO 1.5 TIMES THE DESIGN |
| | PRESSURE. DADE COUNTY & SBCCI REPORTS |
| | ARE ACCEPTED. |
| | |
| | 1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | |
| | 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. |
| | |
| | 1606.4.4 ANCHOR METHODS. PROVIDE |
| | INFORMATION FOR INSTALLATION OF DOOR |
| | AND WINDOW BUCKS. IF THE DESIGNER ISN'T |
| | GOING TO HAVE WINDOW BUCKS, PRODUCT TEST |
| | ING REPORTS FOR WINDOWS WILL HAVE TO |
| | INDICATE A FLANGED FASTENING SYSTEM. THE |
| | OTHER ISSUE WILL BE THE MINIMUM DISTANCE |
| | STORM SHUTTERS WILL HAVE TO STAND OFF |
| | FOR DEFLECTION, USALLY 2 1/2" TO 3". |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)659-8096 X 8412 |
| | FAX: (561)659-8026 |