| 2002-11-19 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE, SERVICE ENTRANCE | | | NEUTRAL SHOWN AS #3? PLEASE NOTE | | | IN ORDER TO HAVE NEUTRAL SIZED MORE- | | | THAN TWO SIZES DOWN, PLEASE PROVIDE | | | NEUTRAL LOAD CALCULATION. | | | 220 NEC | | | | | | 2)NOTE: PLEASE NOTE, AIC RATING IS SHOWN | | | FOR MAIN AND PANELS ARE SHOWN W/ NOTE | | | TO GET INFO FROM FPL. PLEASE NOTE, | | | SERIES RATING FOR PANELS NEED TO BE ON | | | PLANS. CALL FOR ANY QUESTIONS. | | | | | | 3)NOTE: PLEASE NOTE, CIRCUITS ARE STILL | | | BEING SHOWN CROSSING OVER INTO OTHER | | | SPACES. (WATER HEATERS). 210-25 | | | | | | 4)NOTE: PLEASE NOTE COLD WATER PIPE TO | | | BE PART OF GROUNDING ELECTRODE SYSTEM | | | 250-50. | | | | | | 5)NOTE: PLEASE LIST THE REQ`D BATH | | | CIRCUIT(S) PER 210-52D/210-11-C3. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|