 ****2ND REVIEW****
 BUILDING PLAN REVIEW
 PERMIT: 02060667
 ADD: 509 FLAMINGO DR
 CONT: WELLINGTON REMODELING INC
 TEL: (561)798-3330
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 THIS REVIEW SHALL BE COMPLETED UNDR THE
 SECTION 3401.5.4(2) ADDITIONS TO HISTOR-
 ICAL BUILDINGS.
  
 1) THE NEW OPEN STAIRWAY ON THE WEST
 ELEVATION IS CONSIDERED (NEW WORK), NOT
 COVERED BY THE HISTORICAL REVIEW BOARD!
 1006.2.2 PORCHES, GALLERIES, BALCONIES,
 AND EXTERIOR STAIRWAYS SHALL BE LOCATED
 AT LEAST 10' FROM ADJACENT PROPERTY
 LINES AND FROM OTHER BUILDINGS ON THE
 SAME LOT.
 HISTORICS INDICATED THAT THIS IS
 NEW WORK, WHICH REQUIRES THE OPEN STAIR-
 WELL TO BE A MINIMUM OF 10' FROM THE
 PROPERTY LINE!!!!
  
 2) SHEET A.3 THE GARAGE INDICATES A NEW
 SIDE EGRESS DOOR LOCATED ON THE EAST
 SIDE OF THE BUILDING, 2.9' FROM THE PROP
 ERTY LINE. TABLE 600 EXTERIOR BEARING &
 NONBEARING WALLS UNDER 3' FROM THE
 PROPERTY LINE SHALL HAVE NO OPENINGS, IF
 THEY ARE EXISTING THEY ARE GRANDFATHERED
 IN, NO NEW OPENINGS.
  
 3)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 HISTORICS INDICATED THAT THE ONLY SECTIO
 NS THAT ARE OF VALUE IS THE EXISTING
 EXTERIOR STUCCO, HOW SHALL THE EXTERIOR
 FRAME WALLS BE DEMOLISHED AND STILL
 MAITAIN THE STUCCO? HOW WILL THIS BE SHO
 RED? HOW WILL THE STUCCO BE TIED TO THE
 NEW FRAME WALL?
  
 4)2305.2.2 FLOOR/CEILING ASSEMBLIES
 SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/
 ING ASSEMBLIES SEPERATING USEABLE SPACE
 INTO 2 OR MORE APPROXIMATE AREAS WITH NO
 AREA GREATER THAN 500 SQ FT. DRAFTSTOP-
 PING SHALL BE PROVIDED PARALLEL TO THE
 MAIN FRAMING MEMBERS.
  
 5) 704.3 TENANT FIRE SEPERATION,INDICATE
 THE UL LISTING FOR FIRE SEPERATION FOR
 ALL TENANT WALL AND FLOORCEILING ASSEMBL
 IES?
  
 6)705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
 7)1503.3 COPING. PARARET WALLS SHALL
 BE PROPERLY COPED WITH NONCOMBUSTIBLE
 MATERIALS OF A WIDTH NO LESS THAN THE
 THICKNESS OF THE PARAPET WALL. A.5 DE-
 TAILS 5& 6 DO NOT INDICATE THE TYPE
 OF MATERIALS TO BE USED FOR THE COPING?
 NOR TYPE OF ROOFING MATERIALS?
  
 8)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 MISSING THE INTERNAL PRESSURE
 COEFFICIENT OF 0.18
  
 9)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.STRUCTURAL PLAN S.3
 NOTE FOR IMACT RESISTANT GLAZING OR
 STORM SHUTTERS.
 PRODUCT TESTING FOR WIND IS STILL
 REQUIRED EVEN IF STORM SHUTTERS SHALL BE
 USED.
 A) GLAZED OPENINGS
 B) EXTERIOR DOORS
 C)MULLIONS
 D) ROOFING ASSEMBLIES
  
 10) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 11) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 12)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 13) 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 14)1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
  
 15) ARCH NOR STRUC PLANS INDICATE INTER-
 IOR WALL THICKNESS. TABLE 600 EXTERIOR
 WALLS LESS THAN 5'-0" FROM THE PROPERTY
 LINE SHALL COMPLY WITH 709.6.2.1.4.4.
  
 16)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 17) NO STAIR INFORMATION, RISE/ RUN SEE
 FBC 1007.3.1
 1012.5 GROUP R-3 LANDING WIDTH SHALL
 BE NO LESS THAN THE DOOR WIDTH IT SERVES
 AND THE DEPTH SHALL BE NO LESS THAN 36"
 THE LANDING MAY BE ONE STEP LOWER THAN
 THE INSIDE FLOOR LEVEL BUT NOT MORE THAN
 7" LOWER.
 1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
 1608.2.3 THE GUARDRAIL SYSTEM SHALL
 BE DESIGNED AND CONSTRUCTED TO RESIST A
 200 LB CONCENTRATED HORIZONTAL LOAD
 APPLIED ON A 1 SQ FT AREA AT ANY POINT
 IN THE SYSTEM INCLUDING INTERMEDIATE
 RAILS OR OTHER ELEMENTS SERVING THIS
 PURPOSE.
 1007.5.2 STAIRWAYS SHALL HAVE HAND-
 RAILS ON EACH SIDE.
  
 8) FL BLD CODE 2405.2 HAZARDOUS LOCATION
 PROVIDE SAFETY GLASS FOR THIS LOCATION:
 RESIDENTIAL UNIT# 1 BATHROOM.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026