Plan Review Notes
Plan Review Notes For Permit 02060667
Permit Number 02060667
Review Stop P
Sequence Number 1
Notes
Date Text
2002-09-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT A.1 IF UNITS ARE NOT INDIVIDUALLY
 METERED A BACKFLOW SHALL BE REQUIRED FOR
 THE WATER SERVICE TO DETACHED ACCESSORY
 BUILDING.
 2) SHT A.4 PLEASE PROVIDE CALCULATIONS
 FOR ROOF SIZE, AND GUTTER AND DOWNSPOUTS
 SIZE.
 3) SHT M.1 PLEASE PROVIDE A SANITARY AND
 A WATER RISER DIAGRAM. SHOW ALL PIPE
 SIZES. SHOW WATER HAMMER ARRESTOS REQUI-
 RED IN SECTION 604.9. LOCATION SHALL BE
 NEAR FIXTURES PER PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
 4) PLEASE PROVIDE A WATER HEATER DETAIL,
 SHOW DISCHARGE LINE FOR RELIEF VALVE PER
 SECTION 504.7.1, EMERGENCY PAN DRAIN PER
 504.8.1, AND THERMAL EXPANSION CONTROL
 PER 607.3.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377