| Plan Review Notes For Permit 02060667 |
| Permit Number |
02060667 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT A.1 IF UNITS ARE NOT INDIVIDUALLY | | | METERED A BACKFLOW SHALL BE REQUIRED FOR | | | THE WATER SERVICE TO DETACHED ACCESSORY | | | BUILDING. | | | 2) SHT A.4 PLEASE PROVIDE CALCULATIONS | | | FOR ROOF SIZE, AND GUTTER AND DOWNSPOUTS | | | SIZE. | | | 3) SHT M.1 PLEASE PROVIDE A SANITARY AND | | | A WATER RISER DIAGRAM. SHOW ALL PIPE | | | SIZES. SHOW WATER HAMMER ARRESTOS REQUI- | | | RED IN SECTION 604.9. LOCATION SHALL BE | | | NEAR FIXTURES PER PDI-WH 201 AND MANUF. | | | INSTALLATION INSTRUCTIONS. | | | 4) PLEASE PROVIDE A WATER HEATER DETAIL, | | | SHOW DISCHARGE LINE FOR RELIEF VALVE PER | | | SECTION 504.7.1, EMERGENCY PAN DRAIN PER | | | 504.8.1, AND THERMAL EXPANSION CONTROL | | | PER 607.3.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|