Plan Review Notes
Plan Review Notes For Permit 02060667
Permit Number 02060667
Review Stop E
Sequence Number 1
Notes
Date Text
2002-09-17 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT ALL APPLIANCE
 BELONGING TO EACH UNIT NEEDS TO BE THOSE
 UNITS. PLEASE NOTE ELECTRICAL MAY NOT
 CROSS OVER TO OTHER AREAS. PLEASE NOTE
 IF WATER HEATERS MAY BE IN COMMON AREA
 IF COMING FROM HOUSE PANEL. PLEASE
 ALSO NOT AHU FOR DOWNSTAIRS UNIT NEEDS
 TO BE IN THAT UNIT.
  
 2)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FOR EXITING FROM BEDROOM TO COMMON LAUN-
 -DRY ROOM MAY AFFECT ELEC PLANS.
  
 3)NOTE: PLEASE NOTE ALL MAINS MUST BE
 GROUPED PER 230-72.
  
 4)NOTE: PLEASE CLARIFY SERVICE. PLEASE
 NOTE THAT EACH METER IS SHOWN WITH AN
 INDIVIDUAL RISER, PLEASE NOTE ONLY ONE
 SERVICE IS PERMITTED PER 230-2 UNLESS
 A 2 HR SEPARATION IS IN PLACE BETWEEN
 EACH UNIT. PLEASE CLARIFY.
  
 5)NOTE: PLEASE NOTE MISSING GROUNDING
 ELECTRODE SYSTEM PER 250-50. PLEASE
 ALSO NOTE SYSTEM MUST ALL ONE AT THAT
 STUCTURE. 250-24 ETC.
 SIZE PER 250-66.
  
 6)NOTE: PLEASE NOTE MISSING SERVICE
 ENTRANCE CONDUCTORS PER 215-5.
  
 7)NOTE: PLEASE NOTE NO SIZE/LOAD SHOWN
 FOR KW RAITNG FOR AHU`S ON MECH PLAN.
 SHOWN AS 5KW W OCP EXCEEDING 150%.?
 8)NOTE: PLEASE SHOW COND UNIT LOCATIONS
 AND DISCONNECTS PER 440-11.
 PLEASE ALSO NOTE RECEPT PER 210-63.
  
 9)NOTE: PLEASE CLARIFY IF DRYER IS GAS
 OR ELEC. SHOWN AS 20A? PLEASE ALSO NOTE
 LAUNDRY SHOWN WITH GFI AND EXTERIOR RECP
 -S?
  
 10)NOTE: PLEASE NOTE PANEL #1 SHOWS NO
 WATER HEATER AND YET IS SHOWN ON PLANS?
  
 11)NOTE: PLEASE CLARIFY HOW BATH AND
 LAUNDRY IN COMMON BATH/GARAGE ARE BEING
 FED? WATER HEATER?(IF ANY)
  
 12)NOTE: PLEASE PROVIDE CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULES.
  
 13)NOTE: PLEASE CLARIFY TWO SMALL APPLI-
 -ANCE CIRCUITS ON HOUSE PANEL?
  
 14)NOTE: PLEASE NOTE KITCHEN COUNTER
 OUTLET SPACING PER 210-52-C-1.
  
 15)NOTE: PLEASE NOTE SD`S ARE TO BE A
 MIN OF 3' FROM BATHS AND KITCHENS PER
 NFPA-72 2-5.2.1.6.
  
 16)NOTE: PLEASE NOTE CALCS SHOW TWO
 PANEL #1`S? MISPRINT?
  
 17)NOTE; PLEASE LIST THE REQ`D BATH
 CIRCUIT(S) ON PANEL SCHEDULE PER 210-52D
 AND 210-11-C-3.
  
 18)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS PER 210-12.
  
 19)NOTE: PLEASE NOTE RISER DIAGRAM SHOWS
 #4`S FEEDING A/C UNITS AND PANEL
 SCHEDULES SHOW #6`S?PLEASE CORRELATE.
  
 20)NOTE: PLEASE ALSO NOTE THAT PER 230-
 -70. NO MORETHAN 8' OF UNPROTECTED
 CONDUCTORS INSIDE BDLG.
  
 21)NOTE: PLEASE NOTE ALL PANELS ARE
 BEING SHOWN W/OUT MAINS? PLEASE SEE
 PREVIOUS COMMENTS ABOUT MAINS BEING
 GROUPED.225-31/230-72
  
 22)NOTE: PLEASE NOTE THAT A WATER HEATER
 IS SHOWN ON PANEL SCHEDULE FOR #4 BUT
 NONE SHOWN ON PLANS? REFER TO NOTE #11.
  
 23)NOTE: PLEASE CLARIFY CIRCUIT BEING
 SHOWN ON PANEL SCHEDULES AS GFCI LIGHT-
 -ING?
  
 24)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FOR CONDUITS FEED-
 -ING A/C UNITS. SIZE PER 250-122.
  
 25)NOTE: PLEASE NOTE FIRE SEPARATION OF
 ELECTRICAL IN WALL FROM GARAGE TO BED-
 -ROOM. PLEASE NOTE DEVICES AND EQUIP-
 -MENT MAY ONLY BE INSTALLED IN SAME
 SPACE IF FIRE WRAPPED/INSULATED. ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE NOTE THAT THERE ARE MANY
 CHANGES THAT ARE NEEDED ON PLANS AND
 THERE MAY BE OTHER COMMENTS AFTER THESE
 CHANGES. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING ME.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 PLEASE NOTE THAT ONLY ONE SET WAS REVIEW
 -ED. PLEASE NOTE A SECOND SET WILL BE
 NEEDED FOR FINAL PERMIT.