| 2002-09-17 00:00:00 | **************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT ALL APPLIANCE |
| | BELONGING TO EACH UNIT NEEDS TO BE THOSE |
| | UNITS. PLEASE NOTE ELECTRICAL MAY NOT |
| | CROSS OVER TO OTHER AREAS. PLEASE NOTE |
| | IF WATER HEATERS MAY BE IN COMMON AREA |
| | IF COMING FROM HOUSE PANEL. PLEASE |
| | ALSO NOT AHU FOR DOWNSTAIRS UNIT NEEDS |
| | TO BE IN THAT UNIT. |
| | |
| | 2)NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | FOR EXITING FROM BEDROOM TO COMMON LAUN- |
| | -DRY ROOM MAY AFFECT ELEC PLANS. |
| | |
| | 3)NOTE: PLEASE NOTE ALL MAINS MUST BE |
| | GROUPED PER 230-72. |
| | |
| | 4)NOTE: PLEASE CLARIFY SERVICE. PLEASE |
| | NOTE THAT EACH METER IS SHOWN WITH AN |
| | INDIVIDUAL RISER, PLEASE NOTE ONLY ONE |
| | SERVICE IS PERMITTED PER 230-2 UNLESS |
| | A 2 HR SEPARATION IS IN PLACE BETWEEN |
| | EACH UNIT. PLEASE CLARIFY. |
| | |
| | 5)NOTE: PLEASE NOTE MISSING GROUNDING |
| | ELECTRODE SYSTEM PER 250-50. PLEASE |
| | ALSO NOTE SYSTEM MUST ALL ONE AT THAT |
| | STUCTURE. 250-24 ETC. |
| | SIZE PER 250-66. |
| | |
| | 6)NOTE: PLEASE NOTE MISSING SERVICE |
| | ENTRANCE CONDUCTORS PER 215-5. |
| | |
| | 7)NOTE: PLEASE NOTE NO SIZE/LOAD SHOWN |
| | FOR KW RAITNG FOR AHU`S ON MECH PLAN. |
| | SHOWN AS 5KW W OCP EXCEEDING 150%.? |
| | 8)NOTE: PLEASE SHOW COND UNIT LOCATIONS |
| | AND DISCONNECTS PER 440-11. |
| | PLEASE ALSO NOTE RECEPT PER 210-63. |
| | |
| | 9)NOTE: PLEASE CLARIFY IF DRYER IS GAS |
| | OR ELEC. SHOWN AS 20A? PLEASE ALSO NOTE |
| | LAUNDRY SHOWN WITH GFI AND EXTERIOR RECP |
| | -S? |
| | |
| | 10)NOTE: PLEASE NOTE PANEL #1 SHOWS NO |
| | WATER HEATER AND YET IS SHOWN ON PLANS? |
| | |
| | 11)NOTE: PLEASE CLARIFY HOW BATH AND |
| | LAUNDRY IN COMMON BATH/GARAGE ARE BEING |
| | FED? WATER HEATER?(IF ANY) |
| | |
| | 12)NOTE: PLEASE PROVIDE CIRCUITING ON |
| | PLANS AND CORRELATE WITH SUBMITTED PANEL |
| | SCHEDULES. |
| | |
| | 13)NOTE: PLEASE CLARIFY TWO SMALL APPLI- |
| | -ANCE CIRCUITS ON HOUSE PANEL? |
| | |
| | 14)NOTE: PLEASE NOTE KITCHEN COUNTER |
| | OUTLET SPACING PER 210-52-C-1. |
| | |
| | 15)NOTE: PLEASE NOTE SD`S ARE TO BE A |
| | MIN OF 3' FROM BATHS AND KITCHENS PER |
| | NFPA-72 2-5.2.1.6. |
| | |
| | 16)NOTE: PLEASE NOTE CALCS SHOW TWO |
| | PANEL #1`S? MISPRINT? |
| | |
| | 17)NOTE; PLEASE LIST THE REQ`D BATH |
| | CIRCUIT(S) ON PANEL SCHEDULE PER 210-52D |
| | AND 210-11-C-3. |
| | |
| | 18)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | PROTECTED CIRCUITS PER 210-12. |
| | |
| | 19)NOTE: PLEASE NOTE RISER DIAGRAM SHOWS |
| | #4`S FEEDING A/C UNITS AND PANEL |
| | SCHEDULES SHOW #6`S?PLEASE CORRELATE. |
| | |
| | 20)NOTE: PLEASE ALSO NOTE THAT PER 230- |
| | -70. NO MORETHAN 8' OF UNPROTECTED |
| | CONDUCTORS INSIDE BDLG. |
| | |
| | 21)NOTE: PLEASE NOTE ALL PANELS ARE |
| | BEING SHOWN W/OUT MAINS? PLEASE SEE |
| | PREVIOUS COMMENTS ABOUT MAINS BEING |
| | GROUPED.225-31/230-72 |
| | |
| | 22)NOTE: PLEASE NOTE THAT A WATER HEATER |
| | IS SHOWN ON PANEL SCHEDULE FOR #4 BUT |
| | NONE SHOWN ON PLANS? REFER TO NOTE #11. |
| | |
| | 23)NOTE: PLEASE CLARIFY CIRCUIT BEING |
| | SHOWN ON PANEL SCHEDULES AS GFCI LIGHT- |
| | -ING? |
| | |
| | 24)NOTE: PLEASE NOTE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS FOR CONDUITS FEED- |
| | -ING A/C UNITS. SIZE PER 250-122. |
| | |
| | 25)NOTE: PLEASE NOTE FIRE SEPARATION OF |
| | ELECTRICAL IN WALL FROM GARAGE TO BED- |
| | -ROOM. PLEASE NOTE DEVICES AND EQUIP- |
| | -MENT MAY ONLY BE INSTALLED IN SAME |
| | SPACE IF FIRE WRAPPED/INSULATED. ETC. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. PLEASE NOTE THAT THERE ARE MANY |
| | CHANGES THAT ARE NEEDED ON PLANS AND |
| | THERE MAY BE OTHER COMMENTS AFTER THESE |
| | CHANGES. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING ME. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |
| | |
| | PLEASE NOTE THAT ONLY ONE SET WAS REVIEW |
| | -ED. PLEASE NOTE A SECOND SET WILL BE |
| | NEEDED FOR FINAL PERMIT. |