Plan Review Notes
Plan Review Notes For Permit 02060667
Permit Number 02060667
Review Stop B
Sequence Number 1
Notes
Date Text
2002-09-30 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02060667
 ADD: 509 FLAMINGO DR
 CONT: WELLINGTON REMODELING INC
 TEL: (561)798-3330
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PLANS ARE OF A CONCEPTIAL DESIGN,
 NOT ENOUGH INFORMATION TO DO A THOROUGH
 REVIEW.
 THIS REVIEW SHALL BE COMPLETED UNDER THE
 SECTION 3401.5.2 HISTORIC BUILDINGS.
 ALSO INCLUDED SHALL BE 3401.5.4.(2)
 ADDITIONS TO HISTORIC BUILDINGS.
  
 2) THE NEW OPEN STAIRWAY ON THE WEST
 ELEVATION IS CONSIDERED (NEW WORK) NOT
 COVERED BY THE HISTORICS, TO MEET CUR-
 RENT CODES. 1006.2.2 PORCHES, GALLERIES,
 BALCONIES AND STAIRWAYS SHALL BE LOCATED
 AT LEAST 10' FROM ADJACENT PROPERTY
 LINES AND FROM OTHER BUILDINGS ON THE
 SAME LOT, UNLESS OPENINGS IN SUCH
 BUILDINGS ARE PROTECTED BY 3/4 HR FIRE
 RESISTANT DOORS & WINDOWS.
  
 3) 411.2.8 OPENINGS FROM A PARKING GA-
 RAGE DIRECTLY INTO A ROOM USED FOR SLEEP
 ING PURPOSES SHALL NOT BE PERMITTED. SEE
 RESIDENTIAL UNIT # 1.
  
 4) 1007.2(2) STAIRS SHALL HAVE LANDINGS
 AT DOOR OPENINGS, EXCEPTION WHEN THE
 DOOR DOES NOT SWING OUT OVER THE STAIRS.
 BEDROOM UNIT# 1 TO GARAGE.
  
 5) SHEET A-5 INDICATES EXISTING 8"X8"
 EXISTING FOOTING, SHEET A-6 INDICATES
 A NEW FOUNDATION, BUT NO REFENCE AS TO
 WHERE IS GRADE? A SECOND WALL SECTION
 (INTERIOR) INDICATES A VERTICAL FRAMING
 SECTION THAT STOPS ATOP OF A FOUNDATION?
 NO INFO FOR FOUNDATION, NO INFO ON WALL
 SECTION, PT? BOTTOM OR TOP PLATE? STEM
 WALL??????THIS SAME DETAIL DOES NOT
 INDICATE TIE DOWN STRAPPING TO THE
 FOUNDATION. HISTORICS INDICATED THAT THE
 ONLY SECTIONS THAT ARE OF VALUE IS THE
 EXISTING EXTERIOR STUCCO, HOW SHALL THE
 EXTERIOR FRAME WALL BE DEMOLISHED AND
 STILL MAINTAIN THE STUCCO? HOW WILL THIS
 BE SHORED? HOW WILL IT BE TIED BACK TO
 THE NEW BEARING WALL? WHAT SIZE ARE THE
 FLOOR FRAMING MEMBERS?
 DETAILS ALSO MISSING ON THE FIRE
 BLOCKING REQUIRED AT CEILING LEVELS, AS
 WELL AS DRAFT STOPPING EVERY 500 SQ FT
 IN THE SECOND FLOOR ASSEMBLY.
  
 6) 704.3 TENANT FIRE SEPERATION, INDI-
 CATE UL LISTING FIRE SEPERATION FOR WALL
 AND FLOOR CEILING ASSEMBLIES? ALSO SEE
 704.3.2 USABLE CRAWL SPACE!
  
 7) 705.5.1 PENETRATIONS OF FIRE RATED
 WALLS/ 705.6 PENETRATIONS OF HORIZONTAL
 ASSEMBLIES. INDICATE THE UL LISTING.
  
 8)1503.3 COPING. PARARET WALLS SHALL
 BE PROPERLY COPED WITH NONCOMBUSTIBLE
 MATERIALS OF A WIDTH NO LESS THAN THE
 THICKNESS OF THE PARAPET WALL.
  
 9)1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 10)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7.
  
 11) FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 12) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 13)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST. MISSING REPORTS:
 A) GLAZED OPENINGS
 B) EXT. DOORS
 C) ROOFING ASSEMBLIES
  
 14)SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.
  
 15)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 16)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 17) 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 18)1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
  
 19) TABLE 600 LESS THAN 5'-0" FROM
 PROPERTY LINE SEE SECTION 709.6.2.2.
 709.6.2.2 THE FIRE RESISTANCE RATING OF
 A WOOD FRAMED ASSEMBLY IS EQUAL TO THE
 SUM OF THE TIME ASSIGNED TO THE MEMBRANE
 ON THE FIRE EXPOSED SIDE, THE TIME
 ASSIGNED TO THE FRAMING MEMBERS AND THE
 TIME ASIGNED FOR ADDITIONAL CONTRIBUTION
 BY OTHER PROTECTIVE MEASURES SUCH AS
 INSULATION. THE MEMBRANE ON THE
 UNEXPOSED SIDE SHALL NOT BE INCLUDED IN
 DETERMINING THE FIRE RESISTANCE OF THE
 ASSEMBLY.
  
 20)1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 21)1608.2.3 THE GUARDRAIL SYSTEM SHALL
 BE DESIGNED AND CONSTRUCTED TO RESIST A
 200 LB CONCENTRATED HORIZONTAL LOAD
 APPLIED ON A 1 SQ FT AREA AT ANY POINT
 IN THE SYSTEM INCLUDING INTERMEDIATE
 RAILS OR OTHER ELEMENTS SERVING THIS
 PURPOSE.
  
 22) 1203.4.2 EVERY TOLIET ROOM SHALL
 HAVE WINDOWS AS SPECIFIED FOR HABITABLE
 ROOMS PROVIDING IN NO CASE LESS THAN 3
 SQ FT OPEN SPACE, OR HAVE APPROVED EQUIV
 ALENT VENTILATION.
  
 23)1204.4 JOINTS. BUILT IN TUBS WITH
 SHOWERS SHALL HAVE WATER-PROOF JOINTS
 BETWEEN THE TUB & WATER RESISTANT WALL.
  
 24)2304.3.4 WOOD JOIST SHALL HAVE 18"
 CLEARENCE FROM THE BOTTOM OF JOIST TO
 EARTH OR ELSE BE PRESSURE TREATED WOOD
  
 25)TABLE 2306.1 PALM BEACH COUNTY
 AMENDMENTS
 ROOF SHEATHING NAILING REQUIREMENTS
  
 ZONE 1 & 28D COMMON
 6" EDGES & 6" INTERMEDIATES
  
 ZONE 38DCOMMON
 4" EDGES & 6" INTERMEDIATES
  
 26)FL BLD CODE 2309.6 ATTIC ACCESS, PRO-
 VIDE ATTIC ACCESS 20"X36".
  
 27)FL BLD CODE 2405.2 HAZARDOUS LOCATION
 PROVIDE SAFETY GLASS FOR THIS LOCATION:
 BEHIND TUBS
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026