| Plan Review Notes For Permit 02060664 |
| Permit Number |
02060664 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-20 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE PROVIDE A LOAD CALCULATION | | | SHOWING EXISTING AND ALL ADDED LOADS. | | | | | | 2} PLEASE LIST THE REQ,D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 3} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE. PER 210-12 | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL; | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 |
|